1.1. GENERAL DESCRIPTION

The SMOR system is a microprocessor based multifunction protection, control and measurement unit. The
SMOR uses a set of algorithms to create a general purpose protection and monitoring unit for power
systems.
The SMOR system is supplied in a 19'' rack case 2 units high. Figure 1 shows a diagram for panel drilling
installation.
All the information and settings of the unit are accessible by means of a computer connected to the serial
port (RS232 or fiber-optic) or using the man-machine interface (MMI), which includes a 20 character keypad
and a two line liquid crystal display (LCD) with 16 character on each line, located on the front of the relay.
This protection system includes the following functions:
a) Protection:
6 overcurrent units arranged in the following way:
- 3 phase units:
- 51PT, Instantaneous, Inverse or definite time.
- 50PH, Instantaneous or definite time.
- 50PL, Instantaneous or definite time.
- 3 ground units:
- 51NT, Instantaneous, Inverse or definite time.
- 50NH, Instantaneous or definite time.
- 50NL, Instantaneous or definite time.
Independent directional supervision adjustment for each overcurrent functions.
Negative sequence overcurrent
Three-phase over and undervoltage
Ground overvoltage (2 levels). NOTE: Only for the SMOR7000 model an open delta input is available.
Over and under frequency
b) Monitoring and Register
Current measurement for each phase and ground.
Negative sequence current measurement.
Measurement of line to line voltages.
Measurement of active and reactive power along with power factor.
Frequency measurement.
Breaker status.
LED indicators - 17 LED display (16 of which can be configured by the user).
Breaker supervision for failure-to-open or failure-to-close (optional, mounted in the additional board).
Breaker health monitoring (ΣI 2 t) per phase.
Phase rotation sequence selection (ABC or CBA).
Maximeter for current and active power.
Built in self-checking unit.
GEK-105593C
GENERAL DESCRIPTION AND
GENERAL DESCRIPTION AND
GENERAL DESCRIPTION AND
GENERAL DESCRIPTION AND
5
APPLICATION
APP
LICATION
APP
APP
LICATION
LICATION

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SMOR-B GEK 105593C and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents