GE SMOR-B GEK 105593C Instructions Manual page 80

Protection, monitoring, analysis, and energy management numerical system
Table of Contents

Advertisement

Level 1
Level 2
DIRECTIONAL
SET. TX
• RECLOSER
TX
GEK-105593C
Level 3
• 59NL PICKUP
• TIME DELAY 59NH
• 51PT
DIRECTIONAL
• 51NT
DIRECTIONAL
• 50PH
DIRECTIONAL
• 50PL
DIRECTIONAL
• 50NH
DIRECTIONAL
• 50NL
DIRECTIONAL
• PHASE ANGLE
• GROUND ANGLE
• V LOSS LOGIC
• 79 STATUS
• NUMBER OF
CYCLES
• RESET TIME
• HOLD MODE
• HOLD TIMER
• 1s RECLOSE
DELAY
• 2n RECLOSE
DELAY
• 3r RECLOSE
DELAY
• 4t RECLOSE
DELAY
• RECL.
CONDITIONS
• INIT
79x 51PT
• INIT
79x 51NT
• INIT
79x 50PH
• INIT
79x 50PL
• INIT
79x 50NH
• INIT
79x 50NL
75
Valid range
• 3 - 100 V in steps
of 1.
• 0.03 - 100.00 s in
steps of 0.01.
• Permitted - Not
permitted
• Permitted - Not
permitted
• Permitted - Not
permitted
• Permitted - Not
permitted
• Permitted - Not
permitted
• Permitted - Not
permitted
• -90º - +90º in
steps of 1º
• -90º - +90º in
steps of 1º
• Permission -
Block
• Permitted - Not
permitted
• 1 - 4
• 0 - 600 s in steps
of 1.
• Yes - No
• 0 - 100 s in steps
of 1.
• 0.10 - 100 s in
steps of 0.01.
• 0.10 - 100 s in
steps of 0.01.
• 0.10 - 100 s in
steps of 0.01.
• 0.10 - 100 s in
steps of 0.01.
• NONE - INH INP
- VB ONLY - VB -
VB & VL
• Enabled -
Disabled
• Enabled -
Disabled
• Enabled -
Disabled
• Enabled -
Disabled
• Enabled -
Disabled
• Enabled -
Disabled

Advertisement