Frequency Measurement; Recloser - GE SMOR-B GEK 105593C Instructions Manual

Protection, monitoring, analysis, and energy management numerical system
Table of Contents

Advertisement

PHASE CURRENTS
Inject the following current values into the relay:
I (Amp)
Angle
Ia
Ib
165
Ic
285
(In is the nominal or rated current for the relay phase current inputs, 5 or 1 Amp)
• Check that the relay measures Ia, Ib, Ic with an accuracy of at least 5%.
• Repeat the test for 60 Hz.
GROUND CURRENTS
• Inject the following current values into the relay:
I (Amp)
Angle
Iground
(In is the nominal or rated current for the relay ground current input, 5 or 1 Amp)
Check that the relay measures Iground with an accuracy of at least 5%.
Repeat the test for 60 Hz.
Apply 110V at 50 Hz through the voltage input corresponding to phase B.
Check that the frequency measured by the relay is inside the range of 49.97 and 50.03 Hz.
NOTE : Check that the inhibition voltage of the frequency units is lower than the applied voltage. If not, the
unit does not measure the frequency.

6.11. RECLOSER

Recloser Settings Group
79 Status
Number of cycles
Reset Time
Hold Mode
Hold Timer
1st Reclose Delay
2nd Reclose Delay
3rd Reclose Delay
4th Reclose Delay
Recl. Conditions
Enable only 51PL function, and set its pick up and timer to the minimum value possible.
1
45
0.1xIn
0.1xIn
0.1xIn
1
0
0.1xIn(gnd)
GEK-105593C
2
0.5xIn
0.5xIn
0.5xIn
2
0.5xIn(gnd)

6.10.2. FREQUENCY MEASUREMENT

Permitted
4
10 sec
NO
15 sec
2.1 sec
4.1 sec
6.1 sec
8.1 sec
Inh. Input
52
3
4
1xIn
2xIn
1xIn
2xIn
1xIn
2xIn
3
4
1xIn(gnd)
5xIn(gnd)