NOTE: The block inputs for the directional units eliminate the directional supervision, converting the units into
non-directional overcurrent functions while the corresponding input is active.
There is also the IRIG-B synchronization input already mentioned.
The diagram of external connections, in figure 7, shows the default input configuration.

2.4.7.2. Outputs

The SMOR system has 13 outputs as follows:
2 trip
2 close
1 alarm
2 groups of 4 configurable outputs with one common per group.
The model with optional expansion board has 4 more outputs, which are configurable and electrically
separate. (See external connections in figure 7)
The outputs are configured using the GE-INTRO configuration software.
The technical characteristics of the outputs are shown in section 4.
The configurable outputs can be programmed using logic based on the internal protection states (pick-ups,
trips, alarms, etc.) The SMOR has 132 different internal states, and these can be used to carry out logical
operations NOT, AND and OR, which gives to the unit a great flexibility.
Function
Unused input
Breaker 52b
Recloser block
Recloser block
Recloser unblock
Reclose initiate
Reclose inhibit
External trigger
PT secondary MCB tripping
Open fail pickup
Active table select0
Active table select1
Open command
Close command
Phase directional blocking
Ground directional blocking
Phase instantaneous blocking
Ground instantaneous blocking
Phase units blocking
Ground units blocking
Voltage units block
Frequency units blocking
Negative sequence units blocking
General blocking
GEK-105593C