COIL 2:
Repeat the previous test for coil 2. Positive should be applied to terminal F7 and negative to terminal E8.
The signal to be checked is "Coil 2 DC Supply Failure".

6.30. MONITORING TRIP CIRCUITS : COIL FAILURE

(Only for models with expansion board)
COIL 1:
• Short-circuit terminals E5, F6 and E6 (common).
• Apply nominal minimum voltage (38 Vdc for "A" models and 88 Vdc for "H" models) to the voltage
supervision input for coil 1. Positive is applied to terminal F5 and the negative to terminal E6.
• Check using GE_LOCAL software that the "Coil 1 Continuity Failure" signal in the internal Status of the
relay is not active.
• Remove the short-circuit between terminals E5 and E6.
• The "Coil 1 Continuity Failure" signal will not become active.
• Remove the short-circuit between terminals F6 and E6.
• After 1 sec, the "Coil 1 Continuity Failure" signal will become active.
COIL 2:
• Repeat the previous test for coil 2. Positive is applied to terminal F7 and negative to terminal E8. The
terminals corresponding to terminals E5, F6 and E6 will be E7, F8 and E8 respectively. The signal to be
checked is "Coil 2 Continuity Failure"
Description
General Settings Group
Relay status
Identification
Frequency
Rated Voltage
CT Phase Ratio
CT Ground Ratio
VT Line Ratio
VT Busbar Ratio
Demand Time
Phase rotation selection
Breaker Settings Group
Breaker Number
Fail to Open time
Fail to Close time
Accumulable I2t Limit
Intg I2t Time selector
I2t Integr. time
Maximum trips in 1 hour
Active Table Settings
# of Active Settings Table
Cold pick-up permission
Change to Table 3 time
Return from Table 3 time
Oscillography Mask
Number of pre-fault cycles
Oscillo. triggers :
Pick-up 51 PT
Pick-up 51 NT
GEK-105593C
Table 11. Customer's settings
MMI/GE-LOCAL
GENERAL SETTINGS
RELAY STATUS
IDENTIFICAT:
FREQUENCY
NOMINAL VOLTAGE
PHASE CT RATIO
GROUND CT RATIO
LINE VT RATIO
BUS VT RATIO
DEMAND TIME
PHASE ROTATION
BREAKER SETTINGS
BREAKER NUMBER
t FAIL TO OPEN
t TAIL TO CLOSE
KI2T LIMIT
KI2T OP. MODE
KI2T INT. TIME
MAX TRIPS 1h
ACTIVE TABLE SET
ACTIVE TABLE
CLP PERMISSION
t CHANGE TABLE
t RETURN TABLE
OSCILLOS MASK
PREFAULT CYCLES
51PT PICKUP
51NT PICKUP
62
USER VALUES