Operations Group - GE SMOR-B GEK 105593C Instructions Manual

Protection, monitoring, analysis, and energy management numerical system
Table of Contents

Advertisement

8.4. OPERATIONS GROUP.

This group allows you to operate the breaker from the keyboard, and also to block or unblock the recloser
and to synchronize the time on the unit. To access this group, press the ACT key when the SMOR is in the
stand-by screen. This takes you to the operations menu and shows the first item on the menu:
This shows that the first item on the operations menu is the function for entering the date and time for the
relay. When the UP/DOWN ARROW keys are pressed the rest of the items on the operations menu appear.
After locating the required operation use the ENT key to select it.
To avoid carrying out operations by mistake the keyboard program requires confirmation of the operation
selected. To confirm, press the 1/Y key and then ENT. To abort the operation press the 3/N key and then
ENT. Pressing CLR is the equivalent of pressing the 3/N key and then ENT, aborting the operation.
If the command is confirmed the result of the operation appears on the screen. With either ENT or CLR you
can accept this message and return to the operations menu.
By way of example, this would be the process for opening the breaker starting from the operations menu;
OPEN BREAKER
If the breaker had not opened the result of the operation shown on the screen would have been "NOT
PERFORMED".
The SMOR can perform the following operations:
Set date/time
Block recloser
Unblock recloser
Oscillography triggering
Reset current maximeter
Screen
59NH PICKUP
59NL PICKUP
79 STATUS
PROTEC. STATUS
ACTIVE TABLE
STATUS 52
DIRECTION A
DIRECTION B
DIRECTION C
DIRECTION G
REM CONNECTION
LOCAL CONNECTION
DATE / TIME STATUS
E2PROM COMM
COMM SETTINGS
PROTECTION LINK
DATE & TIME
DATE/TIME
ENT
GEK-105593C
Possible values
YES - NO
YES - NO
IN /OUT OF SERVICE
IN / OUT OF SERVICE
1:TABLE 1: 2:TABLE 2 3:TABLE 3
OPEN - CLOSE
PERMISSION - BLOCK
PERMISSION - BLOCK
PERMISSION - BLOCK
PERMISSION - BLOCK
IN / OUT OF SERVICE
IN / OUT OF SERVICE
CORRECT
CORRECT
USER - DEFAULT
YES - NO
(SHOWS DATE & TIME)
SET
CONFIRM?
(Y/N)
80
PERFORMED
1/Y

Advertisement

Table of Contents
loading

Table of Contents