Level 1
Level 2
51NT
FUNCTION TX
50PH
FUNCTION TX
50PL
FUNCTION TX
50NH
FUNCTION TX
50NL
FUNCTION TX
46PT
FUNCTION TX
81 FUNCTION
TX
FUNCTION TX
GEK-105593C
Level 3
DEFINITE TIME t
51/67P PICKUP
CURVE
TIME DIAL
DEFINITE TIME t
50/67P PICKUP
TIME DELAY
50/67P PICKUP
TIME DELAY
50/67N PICKUP
TIME DELAY
50/67N PICKUP
TIME DELAY
• 46PT PICKUP
• CURVE
• TIME DIAL
• DEFINITE TIME t
• 81U PICKUP
• TIME DELAY U
• 81O PICKUP
• TIME DELAY O
• INHIBIT V
• 27P PICKUP
27/59
• TIME DELAY 27P
• 59P PICKUP
• TIME DELAY 59P
• 59NH PICKUP
• TIME DELAY 59NL
74
Valid range
0.00 - 100.00 s in
steps of 0.01.
0.2 - 2.4 A in steps of
0.01.
Inverse - Very inv.-
Extrem. inv. -
Definite t
0.05 - 1.00 s in steps
of 0.01.
0.00 - 100.00 s in
steps of 0.01.
1 - 160 A in steps of
0.01.
0.00 - 60 s in steps
of 0.01.
1 - 160 A in steps of
0.01.
0.00 - 60 s in steps
of 0.01.
0.2 - 32 A in steps of
0.01.
0.00 - 60 s in steps
of 0.01.
0.2 - 32 A in steps of
0.01.
0.00 - 60 s in steps
of 0.01.
• 0.1 - 4 A in steps
of 0.01.
• Inverse - Very
Inv.- Extrem. inv.
- definite t
• 0.05 - 1.00 s in
steps of 0.01.
• 0.00 - 100.00 s in
steps of 0.01.
• 40 - 70 Hz in
steps of 0.01.
• 0.00 - 100.00 s in
steps of 0.01.
• 40 - 70 Hz in
steps of 0.01.
• 0.00 - 100.00 s in
steps of 0.01.
• 35 - 110 % in
steps of 1%
• 10 - 260 V in
steps of 1.
• 0.03 - 100.00 s in
steps of 0.01.
• 10 - 260 V in
steps of 1.
• 0.03 - 100.00 s in
steps of 0.01.
• 3 - 100 V in steps
of 1.
• 0.03 - 100.00 s in
steps of 0.01.