Configuration
44
Building Technologies
Fire Safety & Security Products
Linking the fire panels to the NK8237
All fire panels must be linked to the NK8237. Proceed as follows:
1. Select and expand the NK8237 Ethernet to display the
BACnet Client Protocol.
2. Select the node of the first FC20xx/FC72x panel.
3. Drag and drop the selection to BACnet Client Protocol.
A new node appears in the tree under the protocol representing the link.
4. Repeat the last two steps for all the panels of the fire system.
Tip: If several stations have to be linked to the network driver, you can profit of
the Composer grid mode and link all stations in one shot. Just proceed as follows:
Expand the NK8237 Ethernet to display the BACnet Client Protocol.
–
Select the FS20/FS720 system node.
–
Select the Children tab: the list of stations appears.
–
Select all stations: click the first FC20xx/FC72x icon (in the first column, see
–
image below), then press the SHIFT key and click the last icon in the list. Alter-
natively, you can also select one icon after the other keeping the CTRL key
pressed.
Keeping the SHIFT or CTRL key pressed, drag and drop the selected list to the
–
Network Driver. Note that you may wait a little while before the link icon Error!
Objects cannot be created from editing field codes. shows up on the desti-
nation node.
048_DMS_NK8237_ICC_MP4.40_A6V10316241_a_en.doc
06.2011