Configuration
44
Building Technologies
Fire Safety & Security Products
Linking the fire panels to the NK8237
All fire panels must be linked to the NK8237. Proceed as follows:
1. Select and expand the NK8237 Ethernet to display the
BACnet Client Protocol.
2. Select the node of the first FC20xx/FC72x panel.
3. Drag and drop the selection to BACnet Client Protocol.
A new node appears in the tree under the protocol representing the link.
4. Repeat the last two steps for all the panels of the fire system.
Tip: If several stations have to be linked to the network driver, you can profit of
the Composer grid mode and link all stations in one shot. Just proceed as follows:
Expand the NK8237 Ethernet to display the BACnet Client Protocol.
Select the FS20/FS720 system node.
Select the Children tab: the list of stations appears.
Select all stations: click the first FC20xx/FC72x icon (in the first column, see
image below), then press the SHIFT key and click the last icon in the list. Alter-
natively, you can also select one icon after the other keeping the CTRL key
pressed.
Keeping the SHIFT or CTRL key pressed, drag and drop the selected list to the
Network Driver. Note that you may wait a little while before the link icon Error!
Objects cannot be created from editing field codes. shows up on the desti-
nation node.
048_DMS_NK8237_ICC_MP4.40_A6V10316241_a_en.doc
06.2011