Connecting The Voltage Supply - SMA ennexOS SUNNY PORTAL Operating Manual

Table of Contents

Advertisement

SMA Solar Technology AG
8. Plug the six-pole plug into the port X2 on the
product.
6.5

Connecting the Voltage Supply

Danger to life due to electric shock
Under fault conditions, when working on the power supply circuit there may be dangerous
voltages present on the product. This can result in death or serious injury.
• For power supply units with a fixed connection, make sure that a disconnection unit (e.g.
miniature circuit breaker) is present outside the power supply unit.
• For power supply units with a plug connection, make sure that the electrical outlet for the
power supply unit is close to the power supply unit.
• The disconnection unit and the electrical outlet for the power supply unit must be freely
accessible at all times.
Damage to the product due to condensation
If the product is moved from a cold environment to a warm environment, condensation may form
in the product.
• When there is a large temperature difference, wait for the product to reach room
temperature before connecting to the voltage supply.
• Make sure the product is dry.
Additionally required material (not included in the scope of delivery):
☐ 1 power supply unit
☐ 1 AC connection cable
☐ 1 connection cable for the connection of the power supply unit to the product
Requirements for the power supply unit:
☐ Short-circuit current: < 8 A
☐ Nominal output power: 5 W
☐ DC output voltage: 10 V to 30 V
☐ Compliance with the requirements on current sources with limited power in accordance with
IEC 60950
Operating manual
WARNING
NOTICE
6 Connection
EDMM-10-BE-en-20
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Data manager m

Table of Contents