2. Electrical Service Specifications
a. Gas and Steam Models Only
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES:
A.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY .
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
B.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY . For others, calculate/verify
correct breaker size according to appliance amp draw rating and type of breaker used.
C.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
PHASE
VOLTAGE
208
3ø
230
3ø
240
3ø
380
3ø
380
3ø
400
3ø
416
3ø
440
3ø
460
3ø
480
3ø
575
3ø
*
AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.
** 3-Wire is available.
b. Electric Models Only
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES:
A.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY .
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
B.
Circuit breakers are thermal-magnetic (industrial) type ONLY . For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
C.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
PHASE
VOLTAGE
416
3ø
460
3ø
*
AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.
** 3-Wire is available.
GAS AND STEAM
APPROX.
WIRE
AMP DRAW
SERVICE
60 Hz
50 Hz
3
28.3
3
—
31.9
3
26.7
3
16.2
4**
—
16.1
4**
—
16.1
4**
—
16.0
3
14.4
3
13.9
3
13.9
3
11.4
ELECTRIC (126 kW)
APPROX.
WIRE
AMP DRAW
SERVICE
60 Hz
50 Hz
4**
—
191
3
172
22
MINIMUM
Dual Element
WIRE SIZE
—
*
*
—
*
—
*
*
*
*
—
*
—
*
—
*
—
*
MINIMUM
Dual Element
WIRE SIZE
*
—
*
FUSING
CIRCUIT
BREAKER
Time Delay
50
50
50
50
45
45
25
25
25
25
25
25
25
25
20
20
20
20
20
20
20
20
1/23/09
FUSING
CIRCUIT
BREAKER
Time Delay
300
300
225
225
1/23/09