ensto EVB203E Series Installation Instructions Manual

Wallbox

Advertisement

Quick Links

Ensto Wallbox
EVB203E - series
Installation Instructions
ENG
Operation Instructions
RAK133_ENG
4.10.2019
© Ensto 2019

Advertisement

Table of Contents
loading

Summary of Contents for ensto EVB203E Series

  • Page 1 Ensto Wallbox EVB203E - series Installation Instructions Operation Instructions RAK133_ENG 4.10.2019 © Ensto 2019...
  • Page 2: Table Of Contents

    9. Dimension Drawing......................18 10. Technical Information......................18 11. Installation / Commissioning Checklist................20 12. Maintenance / Preventive Maintenance Instructions............ 21 13. RCD/MCB testing instructions................... 21 14. EVB20E Internal Circuit Example..................22 15. Troubleshooting......................... 23 16. Warranty..........................23 RAK133_ENG / © Ensto 2019...
  • Page 3: Ensto Wallbox, Evb203E-Series

    The installation must be done according to the local safety regulations, restrictions, dimen- sioning, rules and standards. • The information provided in this manual in no way exempts the user of responsibility to follow all applicable rules and safety standards. RAK133_ENG / © Ensto 2019...
  • Page 4: Delivery Contains

    Flange KOT21715 Included in the delivery. Note! Cable glands are not included in the delivery. Please order suitable cable glands separately according to the used supply cable sizes, for example Ensto KTM... cable gland series (polyamide or brass). +0.1 -0.1 knock- outs EVTL40.00...
  • Page 5 EVTL43.0E Ground / Floor mounting pole RAK133_ENG / © Ensto 2019...
  • Page 6 EVTL44.00 Adapter for ground mounting Ø54,5 Ø60,3 4 x M12 RAK133_ENG / © Ensto 2019...
  • Page 7: Mounting Instructions

    If the charging station is installed in conditions where there is a risk of rusting, visible metal surfaces must be protected with anti-corrosion agent. min. 400 mm min. 200 mm Recommendation 1200 mm Follow always national regulations and site requirements RAK133_ENG / © Ensto 2019...
  • Page 8: Wall Mounting With Wall Bracket

    Open the front cover lock and remove the front cover. Note! RFID, LED module and antenna cables are attached to the front cover. Be careful not to break any components when you remove the front cover. RAK133_ENG / © Ensto 2019...
  • Page 9 Place the Wallbox on the wall bracket (1). Attach the top of the Wallbox on the wall bracket using the screws included in the delivery (2). Secure the bottom of the Wallbox with the screws included in the delivery (3). RAK133_ENG / © Ensto 2019...
  • Page 10: Ground Mounting On Concrete Casting With Ground Mounting Pole

    Fix the ground mounting pole on the anchor bolts with washers and nuts. Pull the electric cables through the ground mount- ing pole. Attach the Wallbox on the mounting pole. See in- structions on page 14. RAK133_ENG / © Ensto 2019...
  • Page 11: Ground Mounting On Concrete Foundation With Ground Mounting Pole

    Fix the ground mounting pole on the adapter with bolts, washers and nuts. Pull the electric cables through the ground mounting pole. 10. Attach the Wallbox on the mounting pole. See instructions on page 14. RAK133_ENG / © Ensto 2019...
  • Page 12: Ground Mounting On Unimi Concrete Foundation

    The attachment bar should be oriented to allow attachment of the Wallbox into desired position. Lay the cable conduits into the trenches and install conduits to relevant inlets. Ø15 RAK133_ENG / © Ensto 2019...
  • Page 13 13. Fit the mounting pole to the threaded bolts on the adapter. Secure with the nuts included in the delivery. 14. Pull the electric cables through the mounting pole. 15. Attach the Wallbox on the mounting pole. See instructions on page 14. RAK133_ENG / © Ensto 2019...
  • Page 14: Fixing Wallbox On Mounting Pole Evtl43.0E

    Pull the electric cables through the gable glands. Fix the Wallbox and flange KOT21715 on the mounting pole using the screws included in the delivery. Close the extension box hatch, if electrical connections are done in a separate session. RAK133_ENG / © Ensto 2019...
  • Page 15: Electrical Connections

    Stranded cables are recommended in Wallbox installations. MCB/RCD MCB/RCD A combined residual current protection device and a circuit breaker (RCD / MCB) for each charging outlet are integrated in the charger extension box. max. 50mm² Cu/Al Supply RAK133_ENG / © Ensto 2019...
  • Page 16: Commissioning

    If you want to change the default settings, you must connect to Wallbox via web configuration tool to be able to proceed with the commissioning settings. Use Firefox or Windows Explorer web-browser for configuring. Micro USB service port Please see detailed commissioning instructions on https://evwiki.ensto.technology/ RAK133_ENG / © Ensto 2019...
  • Page 17: User Instructions

    When you stop the charging event, the indicator light turns to waving green and you are able to unplug the charging cable. • After you have unplugged, you are logged out from the charging point and the charging point is free for the next user. RAK133_ENG / © Ensto 2019...
  • Page 18: Dimension Drawing

    Dynamic Load Management (DLM) Supply connections and L1, L2, L3, N, PE terminals Cu/Al 2.5–50 mm² Recommended 10 mm² at nominal power Tightening torque Nm: 4 Nm (2.5 - 4 mm²), 12 Nm (6 - 50 mm²) RAK133_ENG / © Ensto 2019...
  • Page 19 High operating temperature, such as direct sunlight, can cause reduced charging current or temporary interruption in the charging procedure Control and Communication Operation mode Standalone / Online Wireless 2G / 3G / 4G Wired Ethernet Protocol OCPP1.5 or OCPP1.6 RAK133_ENG / © Ensto 2019...
  • Page 20: Installation / Commissioning Checklist

    Test the functioning of Mode 3 (from green to blue). Use a Mode 3 tester. Test the function of the RCD / MCB. Ready for Correct SW is in use. Correct operating mode is in use: • Standalone • Online RAK133_ENG / © Ensto 2019...
  • Page 21: Maintenance / Preventive Maintenance Instructions

    Test the function of the RCD / MCB twice a year. 13. RCD/MCB test instructions Press the TEST button. • The rocker turns to 0 position. • • Turn the rocker back to I position. • If a fault occurs, contact an electrician. RAK133_ENG / © Ensto 2019...
  • Page 22: Evb20E Internal Circuit Example

    BU/RD BU/BN BU/BN BU/BN BU/BN BU/GN BU/GN BU/GN BU/GN BU/YE BU/YE BU/YE BU/YE 6 7 8 9 10 6 7 8 9 10 Emergency Emergency Opener Opener TYPE2 TYPE2 MCB/RCD MCB/RCD max. 50mm² Cu/Al Supply RAK133_ENG / © Ensto 2019...
  • Page 23: Troubleshooting

    “Device Manager” that the established via web browser. RNDIS network adapter is available. If not, up- date the related Windows driver. 16. Warranty Warranty conditions, see the product card on www.ensto.com. RAK133_ENG / © Ensto 2019...
  • Page 24 Ensto Finland Oy Ensio Miettisen katu 2, P.O. Box 77 FIN-06101 Porvoo, Finland Tel. +358 20 47 621 Customer service +358 200 29 007 ensto@ensto.com...