Control Connections - Lenze L-force Mounting Instructions

Table of Contents

Advertisement

Available languages

Available languages

4.6

Control connections

)
Note!
The sums of all inputs currents and output currents on X41, X42, X45, X60 and
X72 may be max. 1.3 A.
If the total current is higher, the device switches off!
Digital inputs
X41 − digital inputs E1, E2
Pin
Signal
1
+24 V
2
Signal 2
3
GND
4
Signal 1
X42 − digital inputs E3, E4
Pin
Signal
1
+24 V
2
Signal 2
3
GND
4
Signal 1
EDKLCMZ3024−SPS DE/EN 4.0
Description
Supply
E2
Reference potential
E1
Description
Supply
E4
Reference potential
E3
l
Electrical installation
Control connections
Data
Connector: socket, 4−pole, M12
HIGH
+13 .... 26.5 V DC
LOW
0 ... +4 V
8 mA at 24 V DC
Data
Connector: socket, 4−pole, M12
HIGH
+13 .... 26.5 V DC
LOW
0 ... +4 V
8 mA at 24 V DC
4
lcu12x_000e
63