Nice NEOSTAR T Series Instructions And Warnings For The Fitter page 3

Tubular motor
Hide thumbs Also See for NEOSTAR T Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
The motor's electrical "up" and "down" phases are interchangeable,
since the former causes the motor to rotate in one direction, the lat-
ter in the opposite direction. The up and down movements are
determined by the side from which the motor is inserted in the wind-
ing tube. The electronic limit switch system establishes and
"assigns" the electrical UP phase only during the programming oper-
ations.
2.2) Connector and power supply cable
personnel only).
!
WARNING: if the power cord is damaged it must be replaced with an identical type supplied by the manufacturer or
an authorised customer service centre.
If it is necessary to disconnect the motor from the power supply cable proceed as shown in the figures below:
Rotate the lock ring until the
notch matches one of the latch-
on teeth, then release.
3) Adjustments
The NEOSTAR_T series tubular motors are equipped with an elec-
tronic limit switch which interrupts the power supply when the
awning reaches its opening or closing limits, corresponding to the
fully rolled up position (0) or fully extended position (1).
These two positions must be programmed into the memory after the
motor has been installed and the awning mounted.
Awning closed (position 0)
(this section refers only to the NEOSTAR MT version and concerns customer service
Repeat the operation for the oth-
er tooth.
Awning open (position 1)
Keep in mind that for the electronic limit switch system the UP and
DOWN phases are not identical; for example, the RDC torque reduc-
tion takes place only during the UP manoeuvre.
Except for the programming operations, it is possible to connect
multiple NEOSTAR_T motors in parallel so as to utilise a single
reverser switch.
Bend the cable towards the
inside and remove the protection
by rotating it gently towards the
outside.
The motor can still be controlled even if these two positions, "0" and
"1", have not yet been memorised; however, the movement in this
case will be interrupted momentarily at the start of each manoeuvre
and will then continue unimpeded and uncontrolled.
It is also possible to program the activation/deactivation of the RDC
torque reduction function during the closing operation.
RDC torque reduction start position for the
Pull out the connector.
closing operation
GB
3