Technical data

9.1

General technical data

Article number
Weight without mounting bracket
Power supply
Short voltage interruption
Power consumption
Noise emission
Degree of protection
Protection class
Degree of pollution
Quality assurance
Note
Note the following if you are operating the device in accordance with IEC/EN/UL 61010-2-
201:
• The device must only be connected to a 24 V DC power supply that meets the
requirements of a safety extra low voltage (SELV/PELV) in accordance with
IEC/EN/UL 61010-2-201.
• In the area in which UL/CSA 61010-2-201 applies, the device must be supplied with
power during operation outside an enclosure according to UL/CSA 61010-2-201 with
NEC Class 2 or a limited-energy circuit according to UL/CSA 61010-1.
7KN POWERCENTER 3000
Manual, 10/2019, L1V30579222003-01
See order documents
Standard: approx. 482 g with DIN rail adapter
24 V DC (19.2 ... 28.8 V)
Up to 5 ms backup time at full load
Max. 10 events per hour; recovery time min. 1 s
max. 1.8 A at 24 V
<40 dB (A) according to DIN 45635-1
IP40 according to IEC 60529
Protection class I according to IEC 61140
Device is designed for environment with pollution de-
gree 2
According to ISO 9001