Permissible Mounting Positions; Upright Mounting - Siemens SENTRON 7KN POWERCENTER 3000 Manual

Iot data platforms
Hide thumbs Also See for SENTRON 7KN POWERCENTER 3000:
Table of Contents

Advertisement

Installing, connecting, commissioning
4.1 Preparing installation
4.1.3

Permissible mounting positions

The following mounting positions are permitted:
● Upright mounting
● Upright mounting on DIN rails
● Wall mounting
● Mounting on DIN rails
Pay attention to the permissible temperature range for operation depending on the mounting
position as stated in chapter Technical specifications (Page 77).
Make sure that the following clearances are maintained from other components or an
enclosure wall:
● Below the device: ≥ 50 mm
● Above the device: ≥ 50 mm
Order numbers for available mounting accessories:
Wall mounting: 6AG4021-0AA20-0AA2
Upright / wall mounting: 6AG4021-0AA20-0AA3
Upright mounting / DIN rail: 6AG4021-0AA20-0AA5
4.1.3.1

Upright mounting

The upright mounting is suitable for vertical mounting of the device. The mounting bracket
provided for this permits, space-saving installation with DIN rail and wall mounting.
22
7KN POWERCENTER 3000
Manual, 10/2019, L1V30579222003-01