b. Heat Tracing and Insulation- Heat Tracing and Insulation only helps in instances where
the customer has the CHC and Heat Tracing on an uninterrupted power source. If the
system is installed without uninterrupted power, and a power failure occurs the
temperature of the piping and system will fall allowing for possible freeze damage.
Here again, the customer's service personnel will be responsible to isolate and drain the
system to protect against freeze damage if the power stays off for extended periods.
Heat Tracing and Insulation also requires for the piping of the skid itself to be protected.
c. Upgraded at Factory with Heated Skid Housings- This level utilizes a heated skid
housing that protects the piping within the skid upon pump failure. The design of the
skid will be modified to internalize the Flow Meter, Conductivity probe and Corrosion
Coupon Rack It requires the use of Heat Tracing and Insulation to protect the piping
from the skid to the towers. This option yields the cleanest installation maximizing
serviceability, however is the most costly of the options.
If you have any questions about Freeze Protection, you can contact EcoWater CHC Technical Services
at 800-722-0476.