5.2.4 Back Pressure Problems-
Verify that the gauges are operating and return to 0 psi as the pump is stopped. If the back
pressure of the CHC chamber is not appropriate the effectiveness of the CHC treatment may be
affected. Increase low CHC back pressures until within range or CHC sound appears. If the
back pressure is too high then decrease the pressure utilizing the back pressure valves on the
discharge of the CHC all the way to any tower isolation valves. Verify that the CHC chamber
is at least within 10' of the water height as long as the back pressure does not exceed 5 psi.
5.2.5 Vacuum Pressure Problems- (When Applicable)
Most vacuum problems are associated with leaks or blocked vacuum tubes.
a.
Leaks- To verify the location of a leak, if you run your hand over the connections of the
tubing and fittings of the vacuum system while the system is running, as you move a
location that is leaking the vacuum will increase, you can then rework that connection or
replace it to fix the problem. In some cases the gauge may be the source of the vacuum
leak. If the gauge has the valve on the back of it, simply close off the valve during
operation of the CHC skid and then turn off the power to the pump if the reading remains
constant then the gauge is not leaking, however, if the pressure decreases quickly, the gauge
or valve will required replacement.
b. Blocked tubing- To verify if the tubing is blocked, first turn off the CHC pump, if the
vacuum changes quickly, there is no blockage. However if the vacuum responds very
slowly or does not change at all, remove the hose from the vacuum gauge and see if the
gauge then responds, if it does the gauge is good and the blockage is somewhere else. The
most common location for blockage is in the vacuum tubes within the chamber, these tubes
will need to be removed and cleaned or replaced. You can also verify that the elbows that
attach to these tubes are free from any buildup, use a descaler (e.g. Rydlyme or equivalent)
to remove the buildup or replace the elbow to correct the problem
c. If you could not find a blockage or leak, you will need to verify the pump pressures and if
correct, the problem is likely associated with the CHC chamber itself. Contact EcoWater
CHC Service Department.
50
Need help?
Do you have a question about the CHC Series and is the answer not in the manual?
Questions and answers