The Control Station has been designed to allow the interface to serve many versions of CHC, Filtration,
alert, function and communication options. Most of the options are build directly into the system and
only require connection to the hardware and Setting Screen Configuration to implement their use.
However the optional communication formats require software modification and are not discussed in
this section.
Pins
Name
+
24 VDC Power
-
Negative
G
Ground
0V
Negative Ref.
A1
Conductivity
A2
Analog Input
A3
Analog Input
A4
Analog Input
I1
CHC Power
I2
Filter Power
I3
CHC Pressure
I4
Filter Pressure
I5
Filter Electrical
I6
CHC Electrical
I7
Filt 1 BW High
I8
Filt 1 BW Low
H1
Filt 2 BW High
H2
Digital Input
H3
Digital Input
H4
Digital Input
C1
Common (R1)
R1
Relay Out 1
C2
Common (R2)
R2
Relay Out 2
C3
Common (R3)
R3
Relay Out 3
C4
Common (R4)
R4
Relay Out 4
C5
Common (R5)
R5
Relay Out 5
C6
Common (R6)
R6
Relay Out 6
Control Station Connections
Function
Supply Positive Power Input
Supply Negative Power Input
Earth Ground
Supply Negative Reference Input
Conductivity Sensor Input (Black wire)
Not Used
Not Used
Not Used
CHC Power Input (24 VDC Signal)
Filter Power Input (24 VDC Signal)
CHC Pressure Input (24 VDC Signal)
Filter Pressure Input (24 VDC Signal)
Filter Electrical Failure Input (24 VDC Signal)
CHC Electrical Failure Input (24 VDC Signal)
Filter 1 BW switch high Input (24 VDC Signal)
Filter 1 BW switch low Input (24 VDC Signal)
Filter 2 BW switch high Input (24 VDC Signal)
Not Used
Not Used
Not Used
Common for Relay 1
Blow Down Relay Control Signal
Common for Relay 2
Filter 1 BW Control Signal
Common for Relay 3
Filter 2 BW Control Signal
Common for Relay 4
Filter 1 Back Pressure Relay Control Signal
Common for Relay 5
Filter 2 Back Pressure Relay Control Signal
Common for Relay 6
Alarm Relay (for Indicator light or BCS integration)
119
Need help?
Do you have a question about the CHC Series and is the answer not in the manual?
Questions and answers