Interrupts, error messages and diagnostics and system alarms
9.3 Diagnostics
9.3.2

Error messages of the Diagnostics Tool

Base image partition test
The following table lists the errors that may occur when testing the partitions of the base
image:
Error message
Partition name can not be read, status: <Value>
Partition size can not be read, status: <Value>
Partition compare failed, status: <Value>
Check SWCPU Index failed, status: <Value>
Software PLC is not found
SWCPU Index is different for the given filesystem The index of the CPU must be "1".
Given path does not exist and whole system does
not contain any SWCPU
Incorrect Path For -m!
No SWCPU with given Index is found
Given SWCPU is using SWCPU from another
filesystem
Partition info mismatch: actual <Value> expected
<Value>
File version consistency test
The following table lists the errors that may occur when testing the Software Controller data
on the third partition (/dev/sda3):
Error message
Can not open file: <File name>
Memory allocation error
File does not exist: <File name>
Hash values are not the same for the file: <File
name>
Expected hash: <Hash value>
Actual Hash: <Hash value>
92
Meaning
Invalid file structure in the mounted path.
One of the first four partitions cannot be found.
The size of one of the first four partitions is inva-
lid.
Valid partition sizes:
sda1: 2 MB
sda2: 198 MB
sda3: 1.3 GB
sda4: 2620 MB
The index of the CPU must be "1".
The fourth partition "/dev/sda4" cannot be found
or is invalid.
The fourth partition "/dev/sda4" cannot be found.
The mounted path does not exist in the file sys-
tem.
The index of the CPU must be "1".
Several memory areas exist on the fourth parti-
tion "/dev/sda4".
The size of one of the partitions is invalid.
Meaning
The file with the hash list cannot be opened. Path
to the hash list:
Boot/Siemens/SWCPU/hash_file
Memory for loading the hash file cannot be as-
signed.
The file cannot be found.
The actual and expected hash values of the file
do not match.
CPU 1505SP (F) Ready4Linux Version 2.7