Siemens SIMATIC S7-1500 Operating Instructions Manual page 56

Software controller cpu 1505sp (f) ready4linux version 2.7
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Commissioning in STEP 7
5.4 Communication between Linux and CPU
Procedure
To establish external Web server access via NAT, proceed as follows:
1. Activate "packet forwarding" with the following command line:
sysctl -w net.ipv4.ip_forward=1
2. To add a rule to the prerouting and postrouting chain, enter the following command lines:
iptables -t nat -A PREROUTING -p tcp -i enp4s0 --src
192.168.2.0/24 --dport 4840 -j DNAT --to-destination 192.168.73.155:4840
iptables -t nat -A POSTROUTING --src 192.168.2.0/24 -j MASQUERADE
Note
Settings are lost after restart
The settings are lost after a restart. To save the setting, you have the following options:
• Use the "iptables-save" and "iptables-restore" commands.
• Install the "iptables-persistent" package.
To check the NAT setting, enter the following command:
iptables -t nat -L
To delete the NAT setting, enter the following command:
iptables -t nat -F
56
enp4s0
Name of the physical network interface assigned to the Linux operating system.
192.168.73.155
IP address of the runtime communication interface
192.168.2.0/24
Address of the subnet of the physical Ethernet interface assigned to the Linux
operating system.
4840
Port number of the OPC UA connection.
CPU 1505SP (F) Ready4Linux Version 2.7
Operating Instructions, 05/2019, A5E46864285-AA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents