Page 1
F043-T TEMPERATURE MONITOR WITH HIGH / LOW TEMPERATURE ALARMS Signal input sensor: Pt100 Alarm output: one temperature alarm Options: Intrinsically Safe F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
The F043-T must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility). • Connect a proper grounding to the metal enclosure as indicated if the F043-T has an incoming power or signal line which carries a hazardous live voltage. The Protective Earth (PE) wire may never be disconnected or removed.
This operation manual describes the standard F043-T as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F043-T is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning !"...
ABOUT THE MANUAL ........................3 WARRANTY AND TECHNICAL SUPPORT ..................3 CONTENTS MANUAL ......................... 4 INTRODUCTION ........................6 System description of the F043-T .................... 6 OPERATIONAL ........................7 General information ......................... 7 Control panel ..........................7 Operator information and functions ..................7 CONFIGURATION ........................
Page 5
Page 5 5.4.1 F043-T-OT-PX-XI-ZB - Ex ia IIC/IIIC ..................31 MAINTENANCE ........................32 General directions ......................... 32 Instructions for repair ......................32 Battery replacement ......................33 6.3.1 Safety instructions ......................... 33 6.3.2 Replace the battery ....................... 34 6.3.3 Disposal of batteries ......................34 TECHNICAL SPECIFICATION .................
Fig. 1: Typical application for the F043-T. Configuration of the F043-T The F043-T has been designed to be implemented in many types of applications. For that reason, a SETUP-level is available to configure your F043-T according to your specific requirements.
Page 7 2 OPERATIONAL GENERAL INFORMATION This chapter describes the daily use of the F043-T. This instruction is meant for users / operators. • The F043-T may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed •...
As soon as the input value is 5% outside the Pt100 measuring range (standard range -100°C - +200°C or extended range type ZV: -200° - +800°C), “RANGE ERROR” will be displayed. • Alarm 01-03 When "alarm" is displayed, please consult Appendix B: problem solving. FW-F043-T-M_v0404_01_EN.docx...
Make sure that the unit is not being used for any application when altering the settings. 3.2.1 ENTERING SETUP-LEVEL Configuration of the F043-T is done at SETUP-level, which can be reached at all times while the F043-T remains fully operational. At SETUP-level the display will deactivate the indicator and...
The combination of the SELECT-key and CLEAR-key is used to select a negative value. When a value can also be entered as a negative number, pressing the SELECT- key and CLEAR-key simultaneously will toggle the ‘–‘ (minus) sign on and off. FW-F043-T-M_v0404_01_EN.docx...
Please keep a record of all settings for later reference. Use the control panel to return to OPERATE-level PROG-key In order to return to the operator level, press the PROG-key for three seconds. When no keys are pressed for 2 minutes, SETUP-level will be left automatically. FW-F043-T-M_v0404_01_EN.docx...
Page 12 CONFIGURATION SETTINGS All settings of the F043-T can be set via the control panel. The following paragraphs give a detailed description of each setting. 3.3.1 OVERVIEW FUNCTIONS SETUP LEVEL SETUP FUNCTIONS AND VARIABLES TEMPERATURE UNIT °C - °F - K OFFSET -999.9 to +999.9 unit...
When used with the internal battery option, the user can expect reliable measurement over a long period of time. The F043-T has several smart power management functions to extend the battery life time significantly. Two of these functions are available.
BATTERY MODE The F043-T has two modes: operational or shelf. After "shelf" has been selected, the F043-T can be stored for several years; it will not process the sensor signal; the display is switched off but all settings and totals are stored. In this mode, power consumption is extremely low.
Operating Manual before carrying out its instructions. • The F043-T may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
The F0-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model code by Type XI (e.g. F043-T-XI). For Intrinsically Safe applications: Installation and identification labels are shown in chapter 5.
Plastic enclosure: 1 Nm per screw Aluminum enclosure: 1 Nm per screw Aluminum w. extended back enclosure: 1 Nm per screw Stainless steel enclosure: 2 Nm per screw 5. The F-Series in now ready to be returned to service. FW-F043-T-M_v0404_01_EN.docx...
0.12" 0.12" M20 x 1,5 3x 1/2"NPT 25mm 25mm 15 15 M20 x 1,5 M20 x 1,5 4x M20 x 1,5 29.1 mm (1.15”) 115 mm (4.53”) 31 mm (1.22”) Fig. 9: Dimensions – Aluminum and stainless steel enclosures FW-F043-T-M_v0404_01_EN.docx...
Meter mount by using one of the openings Pipe mount by using the mounting plate in the bottom of the back cover. with the bracket and hose clamps (accessory). Panel mount by using only the front cover Fig. 11: Installation – Mounting configurations FW-F043-T-M_v0404_01_EN.docx...
General directions: • The F043-T that came with a power module type PM; 110V-230V AC or type PD/PF with an option OR (the relays can handle 110V-230V AC) shall be connected to the Protective Earth (PE) stud which is installed in the metal back panel.
Within the United States all field wiring must conform to the National Electric Code, NFPA 70, Article 501-4(b). All field wiring enters the F043-T through the bottom of the enclosure and connects to the circuit assembly inside the enclosure. Wiring is routed through cable glands. Please make sure to order the F043-T with the correct drilling pattern and thread (metal) or hole (plastic) sizes.
TERMINAL 5-6: POWER SUPPLY - TYPE PX To power the F043-T an internal battery can be used (type PB) and / or an external DC power supply of 8-30V DC (type PX). Connect the "-" to terminal 5 and the "+" to terminal 6.
TERMINAL 9-10: POWER SUPPLY BACKLIGHT - TYPE ZB (OPTION) To power the backlight, a voltage in the range 20-30V DC has to be connected. Maximum current 30mA. Connect the "-" to terminal 9 and the "+" to terminal 10. Fig. 15: Terminal connections - Backlight (ZB). FW-F043-T-M_v0404_01_EN.docx...
The F0-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model code by Type XI (e.g. F043-T-XI). If Type XI is not indicated your device is not suitable for Intrinsically Safe applications!
Ga, the indicator shall be installed so, that even in the event of rare incidents, an ignition source due to impact or friction sparks between the enclosure and iron/steel is excluded. FW-F043-T-M_v0404_01_EN.docx...
The cable parameters are determined by the parameters of the system into which the F0-Series General Purpose Indicators is connected. Only certified Intrinsically Safe Fluidwell battery type FW-LiBat-0xx may be used and replaced in hazardous area. The entity parameters for F0-Series General Purpose Indicators, model F0xx-T-XI, are as follows: Terminals 1, 2, 3 and 4 –...
Ga, the indicator shall be installed so, that even in the event of rare incidents, an ignition source due to impact or friction sparks between the enclosure and iron/steel is excluded. • For EPL Da the ambient temperature Ta shall not exceed 50 °C. FW-F043-T-M_v0404_01_EN.docx...
(terminals 9 and 10) 30 V 0 mH 200 mA 0 nF = 0.75 W From the safety point of view the circuits shall be considered to be connected to earth. FW-F043-T-M_v0404_01_EN.docx...
5.3.1 POWER SUPPLY WIRING The F043-T can be powered from an external power supply. An internal power supply is also available in the form of a lithium battery. When both external and internal power supplies are available, the internal power supply is interrupted and will act as a backup supply. Note that the optional backlight only works with an external power supply.
Fig. 19: F043-T-OT-PX-XI-ZB - Ex ia IIC/IIIC - Intrinsically Safe application. Please note: Type PX may be used in combination with the battery (Type PC). PX will power the F043-T, the battery will be disabled automatically until the power is disconnected. FW-F043-T-M_v0404_01_EN.docx...
(above 90% annual mean). It is the users responsibility to take all precautions to dehumidify the internal atmosphere of the F043-T in such a way that no condensation will occur, for example by placing dry silica-gel sachet in the casing just before closing it.
Safe area applications – Type PB • Before replacing the battery, verify that the new battery is undamaged, in good condition and suitable for use in the unit. (Type: StdLiBAT021 - re-ordering nr. SPB02) Fig. 21: Marking Type PB battery: Safe area StdLiBAT021 (SPB02) FW-F043-T-M_v0404_01_EN.docx...
Dispose of batteries in accordance with the (inter)national, the manufacturer’s and the plant owner’s standards and regulations. • Batteries pose an environmental hazard. • Do not dispose of as general waste or incinerate. • Return used batteries to a recycling point. FW-F043-T-M_v0404_01_EN.docx...
Type HJ Drilling: 3x 22mm (0.87”). Type HK Flat bottom - no drilling. Operating temperature Safe area -40°C to +80°C (-40°F to +178°F). Intrinsically Safe -40°C to +70°C (-40°F to +158°F). For EPL Da: -40°C to +50°C (-40°F to +122°F) FW-F043-T-M_v0404_01_EN.docx...
Page 36
ANSI/UL 60079-0 FM Class 3610 ANSI/UL 60079-11 FM Class 3810 RoHS EN 50581 IEC 63000 IP & NEMA EN 60529 ANSI/IEC 60529 NEMA 250 Note: See the applicable Declaration of Conformity or product certificate for specific revisions and publication dates. FW-F043-T-M_v0404_01_EN.docx...
Page 37
• alarm values can be entered (this function can be disabled) Temperature Digits 6 digits. Unit °C - °F - K Decimals Alarm values Type of alarm Low and/or high temperature alarm. Includes delay time. Digits 4 digits. Unit °C - °F - K Decimals FW-F043-T-M_v0404_01_EN.docx...
Page 38 PROBLEM SOLVING In this appendix, several problems are included that can occur when the F043-T is going to be installed or while it is in operation. Range error • Range error: the input value is at least 5% above or below the measurement range. Check wiring and sensor.
Page 39 DECLARATION OF CONFORMITY eghel, February 2022 e, Fluidwell , declare under our sole responsibility that the F0 eries indicators are designed and will operate conform the following applicable European Directives and armonised tandards, when installed and operated according to the related manuals...
7, 9, 15, 25, 32 alarm color operator level battery low pass code Configuration power supply contents range error 8, 38 dimensions metal enclosures 18, 19 SETUP-level display temperature temperature display update time measuring unit functional description terminal connectors FW-F043-T-M_v0404_01_EN.docx...