Checking The Ignition Ionisation Electrode - Wolf FGB-K Series Installation And Maintenance Instructions For Contractors

Wall mounted gas condensing/combi boiler
Hide thumbs Also See for FGB-K Series:
Table of Contents

Advertisement

28.6. Checking the ignition ionisation
electrode
Replacing the electrodes
- Remove the electrode by releasing the two M4 screws.
- The electrode, including gasket, must be replaced every time maintenance
work is carried out (torque for fixing screws 3.0 ± 0.3 Nm).
Electrode
3064458_201811
68