Wolf FGB-K Series Installation And Maintenance Instructions For Contractors page 78

Wall mounted gas condensing/combi boiler
Hide thumbs Also See for FGB-K Series:
Table of Contents

Advertisement

Balanced flue
Flue gas routing options
Flue in a shaft and combustion air
B23P
directly via boiler (open flue)
Flue in a shaft with horizontal,
B33P
concentric connecting pipe (open flue)
Connection to moisture-resistant chimney
B33P
with horizontal concentric
connecting pipe (open flue)
Horizontal roof outlet through pitched roof
C13x
(balanced flue – on-site dormer)
Vertical concentric roof outlet through pitched or flat roof,
C33x
vertical concentric balanced flue system for installation
in a shaft (room sealed)
Connection to moisture-resistant room sealed balanced flue chimney,
C43x
maximum pipe length from centre of boiler bend to
connection 2 m (room sealed)
Connection to flue in a shaft and ventilation air supply through external wall
C53
(room sealed), 3 m ventilation air duct incl.
Connection to flue on external wall, combustion air intake via external wall
C53x
(room sealed)
Connection to flue in a shaft and ventilation air through external wall
C83x
(room sealed)
Concentric connection to moisture-resistant flue
C83x
gas chimney and combustion air
through external wall (room sealed)
Flue for installation in a shaft,
C93x
connecting pipe DN60/100, vertical DN60
Flue for installation in a shaft, vertical DN80
connecting pipe DN60/100
C93x
connecting pipe DN80/125
connecting pipe DN80/125
The maximum length corresponds to the total length from the appliance to the flue terminal.
1)
For available lifting pressures of gas blowers, see specification.
Note: Systems C33x and C83x are also suitable for
installation in garages.
Where necessary, adapt the installation examples to the
relevant building regulations and requirements in your
country/region. Any questions relating to the installation,
particularly regarding the provision of inspection
components and ventilation apertures (ventilation generally
required above 50 kW output) should be raised with your
local flue gas inspector prior to installation.
The specified lengths refer to concentric balanced
flues and standard flues, and apply to original Wolf
components only.
Balanced flue systems DN60/100 and DN80/125
are certified as single units together with Wolf gas
condensing boilers.
78
31. Technical information, balanced flue
DN60/100
DN80/125
DN60/100
DN80/125
DN110/160
DN80/80
DN60/100
DN80/125
DN80/125
The following balanced flues or standard flues with
CE-0036-CPD-9169003 certification may be used:
- Flue pipe DN80
- Concentric balanced flue DN60/100 and DN80/125
- Flue pipe DN110
- Concentric balanced flue (on external walls) DN80/125
- Flexible flue pipe DN83
Wolf accessories are supplied with the relevant necessary
identification labels.
Please also observe the installation information supplied
with the accessories.
Maximum length
[m]
up to
up to
28 kW
35 kW
DN60
11
7
DN80
50
50
DN60
9
5
DN80
50
50
Calculation to EN 13384
(room sealed balanced
flue manufacturer)
5
3
10
10
6
4
18
29
19
48
Calculation to EN 13384
(room sealed balanced
flue manufacturer)
50
50
9
5
50
50
50
50
Calculation to EN 13384
(room sealed balanced
flue manufacturer)
rigid
8
5
rigid
14
27
rigid
15
39
flexible
14
37
3064458_201811