5. Connecting the conductor end

Several possibilities of how to connect
will be described below.
In the connection area, an adjustment area must be observed around the
to 5d). No electrical, conductive or earthed parts may be located in this area to ensure that lightning currents
are safely conducted into the conductor.    

Case 1

In this case, connection to the equipotential bonding system is not required. A spacer with an insulating
clearance of 910 mm (Part No. 106 812) is installed at a distance of 1200 mm (measured from the connection
element).
The adjustment area shown in Fig. 5a must be maintained.
The equivalent separation distance is s ≤ 45 cm (in air).
separation distance s ≤ 45 cm
r ≥ 45 cm
roof parapet
Fig. 5a
Case 1 without connection to the equipotential bonding system (s ≤ 45 cm)
HVI light Conductors
120 cm
r ≥ 45 cm
1
11
to the air-termination system/roof parapet
HVI light Conductor
- GRP spacer, Part No. 106 812
GRP length = 1000 mm, plastic bushing,
1
plastic conductor holder (Ø 20 mm)
- Concrete base e.g. Part No. 102 340
- FB roof conductor holder, Part No. 253 015
2
- Adapter (Ø 20 mm), Part No. 253 026
l ≥ 45 cm
No electrical, conductive or
earthed parts may be located in
this adjustment area, the
separation distance „s" must be
HVI light Conductor
2
Publication No. 1637/ UPDATE 07.19 Mat-No. 3003103
(Figs. 5a
maintained!