Case 3

In this case (Fig. 5c), the equipotential bonding connection element is installed at a distance of 120 cm
(measured from the connection element) and is connected to the equipotential bonding system. To this
end, the outer grey sheath of the
bonding connection element contacts the black sheath underneath it. This black sheath may not be
damaged. The equipotential bonding connection element must be connected to the equipotential
bonding system of the building by means of a conductor with a cross section of ≥ 4 mm² Cu or
equivalent.
The equivalent separation distance is „s" ≤ 45 cm (in air).
separation distance s ≤ 45 cm
r ≥ 45 cm
roof parapet
Fig. 5c
Case 3 with connection to the equipotential bonding system (s ≤ 45 cm)
HVI light Conductor
120 cm
must be removed so that the equipotential
- GRP spacer, Part No. 106 852
GRP length = 500 mm, plastic bushing,
1
plastic conductor holder (Ø 20 mm)
- Concrete base e.g. Part No. 102 075
- Base plate, Part No. 102 060
- FB roof conductor holder, Part No. 253 015
2
- Adapter (Ø 20 mm), Part No. 253 026
- EB connecting element (Ø 17 mm),
3
Part No. 410 219
3
1
Publication No. 1637/ UPDATE 07.19 Mat-No. 3003103
13
No electrical, conductive or
earthed parts may be located in
this adjustment area, the
separation distance „s" has to be
maintained!