Case 2

As is the case with case 1, no equipotential bonding connection element is required and thus the
Conductor
is not connected to the equipotential bonding system. A spacer with an insulating clearance of
41 cm (Part No. 106 852) is installed at a distance of 120 cm (measured from the connection element). The
adjustment area shown in Fig. 5b must be maintained.
The equivalent separation distance is „s" ≤ 30 cm (in air).
separation distance s ≤ 30 cm
r ≥ 30 cm
roof parapet
Fig. 5b
Case 2 without connection to the equipotential bonding system (s ≤ 30 cm)
120 cm
r
1
2
l ≥ 45 cm
30 cm
1
2
Publication No. 1637/ UPDATE 07.19 Mat-No. 3003103
12
- GRP spacer, Part No. 106 852
GRP length = 500 mm, plastic bushing,
plastic conductor holder (Ø 20 mm)
- Concrete base e.g. Part No. 102 075
- Base plate, Part No.102 060
- FB roof conductor holder, Part No. 253 015
- Adapter (Ø 20 mm), Part No. 253 026
No electrical, conductive or
earthed parts may be located in
this adjustment area, the
separation distance "s" has to
be maintained!