30
Chapter 4 Use Of Monitoring Module M500D
UnderVolt
50V ~ 300V
3-phase,
AC Input
Single Phase,
None
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual
The monitoring module will raise an alarm when the
AC voltage of an operating route is lower than the
80V
"UnderVolt", but there will be no alarm when the AC
voltage of the standby route is lower than the
"UnderVolt"
Set this parameter according to the actual situation. In a system with an AC sampling
3-phase
board, you can only select "Single Phase" or "3-phase"; in a system without an AC
sampling board, you can select only "None"
The "UnderVolt" must be lower
than the "LowVolt"