Features - Emerson NetSure 501 A50 User Manual

19-inch subrack power supply system
Hide thumbs Also See for NetSure 501 A50:
Table of Contents

Advertisement

Item
Monitoring module
Rectifier
AC power distribution
DC power distribution
Battery MCB
Maximum dimensions
Weight
Optional parts

1.3 Features

The rectifier uses the active Power Factor Compensation (PFC) technology, raising the power factor to 0.99
Wide AC input voltage range: 85V ~ 290V (NetSure 701 A51) or 85Vac ~ 300Vac (NetSure 501 A50 & NetSure
501 AA0)
The rectifier uses soft switching technology, raising the system efficiency to 89% (R48-1800)/ 90% (R48-3200)
Ultra-low radiation. With advanced EMC design, the rectifier meets international standards such as CE and
NEBS. Both the conducted and radiated interference reach Class B
The rectifier safety design complies with UL, CE and NEBS standards
High power density
Rectifiers are hot pluggable. It takes less than 1min to replace a rectifier
Two over-voltage protection methods are optional: hardware protection and software protection. The latter one
also has two optional modes: lock-out at the first over-voltage and lock-out at the second over-voltage
Perfect battery management: The management functions include the LLVD (optional), BLVD, temperature
compensation, auto voltage regulation, stepless current limiting, battery capacity calculation and on-line battery
test, etc
Up to 200 pieces of historical alarm records, and 10 sets of battery test data records
Network design: Providing multiple communication ports (such as RS232, modem, RJ45 and dry contacts),
which enables flexible networking and remote monitoring
Perfect lightning protection at AC side
Complete fault protection and fault alarm functions
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual
Table 1.2 Configuration of fixed- configuration system
NetSure 501 A50
Model: M501D
Model: M501D
Model: R48-1800.
Model: R48-1800.
Standard configuration:
Standard configuration:
5 pieces
10 pieces
3P + N + PE/ 380Vac
3P + N + PE/ 380Vac
BLVD load route: 3 ×
BLVD load route: 5 ×
63A/1P, 3 × 32A/1P, 4 ×
63A/1P, 5 × 32A/1P, 8 ×
10A/1P MCB
10A/1P MCB
No LLVD load route
No LLVD load route
2 × 125A/1P
2 × 125A/1P
483 (W) × 380 (D) × 267
483 (W) × 380 (D) × 490
(H)
(H)
25kg (not including
30kg (not including
rectifiers and monitoring
rectifiers and monitoring
module)
module)
Temperature sensor and connected cables, remote monitoring unit, battery rack
NetSure 701 A51
NetSure 501 AA0
(PS48300-3A/3200)
Model: M501D
Model: R48-3200.
Standard configuration:
5 pieces
3P + N + PE/ 380Vac
BLVD load route: 5 ×
63A/1P, 5 × 32A/1P, 8 ×
10A/1P MCB
No LLVD load route
2 × 125A/1P
483 (W) × 380 (D) × 445
(H)
25kg (not including
rectifiers and monitoring
module)
Chapter 1 Overview
3
NetSure 701 A51
(PS48300-3A/3200-X2)
Model: M500D
Model: R48-2900U.
Standard configuration: 3
pieces
P + N + PE/ 230Vac
BLVD load route: 4 ×
40A/1P, 1 × 10A/1P MCB
No LLVD load route
2 × 125A/1P
483 (W) × 380 (D) × 311
(H)
25kg (not including
rectifiers and monitoring
module)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netsure 701 a51Netsure 501 aa0

Table of Contents