Commissioning - Bosch Rexroth IndraControl L25 Instruction Manual

Table of Contents

Advertisement

DOK-CONTRL-IC*LX5*****-IT01-EN-P
Rexroth IndraControl L25, L45, L65 and L85 Controls
11

Commissioning

General Information
Commissioning steps
NOTICE
Do not remove the Compact Flash card as long as the control is in operation!
For commissioning the control, further parameterization or programming is
necessary.
Proceed as follows to commission the control:
1.
Mounting the control
(For details, please refer to
Electrical Installation" on page
2.
Insert the Compact Flash card with approved firmware
3.
Connect the power supply via the connectors from the connector set
For details, please refer to
Control" on page 38
4.
Switch on the control
NOTICE
Ensure that, depending on the software variant, " HW init" is displayed
after the control has been switched on. Wait unit the procedure is com‐
pleted (approx. 20 seconds). Do not switch off the control. During this
time an update is running. This procedure has to be completed. After
this the commissioning can be continued.
5.
If necessary, use a lithium battery for the optional SRAM memory, see
also
chapter 5 "Spare Parts, Accessories, and Wear Parts" on page 13
and
chapter 14.4 "Lithium Battery" on page 53
6.
If necessary, make other settings (IP address, subnet mask, gateway
address, ...) at the display. For further information, please refer to the
description of the relevant system (MLC, IndraLogic, MTX, MLC, XLC).
Bosch Rexroth AG
Production failure due to uncontrolled ma‐
chine movement, caused by operation with‐
out Compact Flash card or by removal of the
Compact Flash card during operation.
chapter 10 "Mounting, Dismounting and
25)
chapter 10.7.3 "Voltage Supply for the
and the relevant project planning manuals
Possible production failure due to mal‐
function of the control if the control has
been switched off during the update
process.
47/65