Bosch Rexroth IndraControl L25 Instruction Manual page 20

Table of Contents

Advertisement

18/65
Bosch Rexroth AG
Technical Data
Voltage supply and current, power
consumption
Degree of protection
IP 20
Dimensions
See
Fig.7-1:
Technical data
The control is supplied with 24 V. The following values according to
DIN EN 61131-2 apply to the operating voltage:
Nominal voltage
Tolerance
Residual ripple
U
max
U
min
Power consumption of the controls from
U
at nominal voltage and all connected
LS
function modules and Inline terminals
Current consumption of the controls from
U
and U
M
S
Power consumption (typically) of the con‐
trols (without connected I/O and function
modules)
Fig.7-2:
Operating voltage and current, power consumption
Three operating voltages (segment voltage U
the main voltage U
) are to be applied to the control, see also
M
"24 V Voltage Supply" on page
NOTICE
Ensure that a ground terminal is always connected. In this way malfunctions
that are caused by feed backwards via I/O signals can be avoided.
DOK-CONTRL-IC*LX5*****-IT01-EN-P
Rexroth IndraControl L25, L45, L65 and L85 Controls
chapter 10.2 "Housing Dimensions" on page 26
DC 24 V
-15 %, +20 % (without residual ripple)
±5 %
30 V
19.2 V
Control L25: 2 A max.
Control L 45: 2.6 A max.
Control L65: 3.0 A max.
Control L85: 3.0 A max.
Max. 8 A in total
Control L25: 8.7 W
Control L45: 14 W
Control L65: 18 W
Control L85: 21 W
, the supply voltage U
S
40.
Possible production failures due to malfunc‐
tions caused by feed backwards due to un‐
connected ground terminal.
and
LS
chapter 10.7.4