Ambient Conditions - Bosch Rexroth IndraControl L25 Instruction Manual

Table of Contents

Advertisement

DOK-CONTRL-IC*LX5*****-IT01-EN-P
Rexroth IndraControl L25, L45, L65 and L85 Controls
6

Ambient Conditions

Notice for control L25
In operation
Max.
surrounding
+5 ℃ to +55 ℃
air temperature
Relative humidity
RH -2; 5 % to 95 %
according to DIN
EN 61131-2,
non-condensing.
Air pressure
Up to 2,700 m
above MSL accord‐
ing to DIN 60204.
Above 2700 m
above MSL, see
chapter 10.7.8
"Notice for Use of
the Control above
2700 m above
MSL" on page
Mechanical
Max. vibration:
strength
Frequency range:
10 Hz to 150 Hz
Excursion:
0.075 mm
at 10 Hz to 57 Hz
Acceleration: 1 g
at 57 Hz to 150 Hz
acc. to EN
60068-2-6
Fig.6-1:
Ambient conditions
The surrounding air must be free from acids, alkaline solutions,
corrosive agents, salts, metal vapors, and other electrically con‐
ductive contaminants in high concentrations.
The ambient air must be dust-free. Housings and installation com‐
partments must at least comply with degree of protection IP 54
according to DIN VDE 0470-1.
NOTICE
Operation is allowed up to 55 ℃ and if the air recirculates. If the air does not
recirculate, the fan has to be used.
If the internal temperature is 87 ℃ or higher, the display indicates the
"Temp !!!" warning.
If the internal temperature reaches approx. 92 ℃, the control switches off au‐
tomatically.
Bosch Rexroth AG
Transport
-25 ℃ to +70 ℃
RH -2; 5 % to 95 %
according to DIN
EN 61131-2,
non-condensing.
Up to 3000 m
above MSL accord‐
ing to DIN 60204.
Above 2700 m
above MSL, see
chapter 10.7.8
"Notice for Use of
the Control above
2700 m above
43.
MSL" on page
43.
Max. shock:
15 g acc. to
EN 60 068-2-27, no
disturbance of the
function.
Production failure possible due to control fail‐
ure resulting from overheating.
15/65
Ambient Conditions
Storage
-25 ℃ to +70 ℃
RH -2; 5 % to 95 %
according to DIN
EN 61131-2,
non-condensing.
Up to 3000 m
above MSL accord‐
ing to DIN 60204.
Above 2700 m
above MSL, see
chapter 10.7.8
"Notice for Use of
the Control above
2700 m above
MSL" on page
43.
Max. shock:
15 g acc. to
EN 60 068-2-27, no
disturbance of the
function.

Hide quick links: