2. Select proper power cable(refer 2.2 power cable table) connect
EBM and UPS. Make sure install a DC breaker(eg.EATON
LZMN1-A160) between UPS and EBM connection. The minimum
rating voltage and rating current of DC breaker not less than below
table.
UPS Type
Battery voltage
Battery current
DANGER: Inorder to avoid hazards shock, do not connect EBM
to UPS Before finish EBM connecting.
3. Connect EBM to UPS, after finish connecting between EBM and
UPS, UPS output does not carry with any load, then turn on EBM
switch to On possiton, and turn on mains power switch, UPS begins
to charge EBM at the time.
Note: Verify the battery connect to UPS with the correct polarity.

2.5 UPS Connect To Computer Port

RS232 interface is for the monitoring software and firmware update.
UPS connect to monitor device with RS232 cable.
1. One end of RS232 cable connects to computer RS232 port.
2. One end of RS232 cable connects to UPS RS232 port.
C6KS
192Vdc
36.5A. Max
- 12 -
C10KS
3C10KS
192Vdc
192Vdc
60.5A. Max
60.5A. Max