*The max current is under 176Vac input, full rating load and empty battery
charging.
Waring: this is a product for commercial and industrial application
in the second environment installation restrictions or additional
measures may be needed to prevent disturbances.
note: It is recommended that the UPS output line is not more than
10m, the external communication line, and the machine line and the
temperature detection line is not more than 3m, otherwise it may
need to take installation restrictions or additional measures to
suppress interference.
Altitude load=Rating load*Altitude correction factor.
Altitude
(m)
Altitude
correction
factor
note: if UPS used over 1000m altitude, the rating must be
derating according to above table.
1000
1500
2000
100%
95%
91%
2500
3000
86%
82%
- 6 -
3500
4000
4500
78%
74%
70%
5000
67%