Advertisement

Quick Links

Thank you for purchasing our products
Please strictly comply with this manual and machine all warning and
the operating instructions and keep this manual. No reading through
all of the safety instruction and the operating instructions before,
please don't operate UPS.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 20k and is the answer not in the manual?

Questions and answers

Summary of Contents for Santak 20k

  • Page 1 Thank you for purchasing our products Please strictly comply with this manual and machine all warning and the operating instructions and keep this manual. No reading through all of the safety instruction and the operating instructions before, please don’t operate UPS.
  • Page 2: Operating Environment

    Safe declare Operation safety 1. In the use of the product before, please read “safety declare”, to ensure the correct and safe to use. And please keep the manual. 2. Pay attention to the all warning when operating, according to the requirements for operation. 3.
  • Page 3: Table Of Contents

    Contents ChapterⅠ Product description......................1-9 1.1 Synopsis...............................1 1.2 Main configuration..........................1 1.3 Operational principle..........................2 1.4 Structure configuration........................2-4 1.5 Operation mode..........................5-6 1.6 Basic function...........................6-7 1.7 Specification.............................7-9 ChapterⅡ Installation........................10-12 2.1 Environmental requirements......................10 2.2 Unpacking............................10 2.3 Mechanical size..........................10-11 2.4 Transport............................11 2.5 Method of fix.............................11 2.6 Terminal Block connect........................12 2.7 Ventilation............................12 ChapterⅢ...
  • Page 4: Chapterⅰ Product Description

    ChapterⅠ Product description 1.1 Synopsis The present specification defines the technical characteristics of the UPS, a device which supplies clean and stable energy to the connected load. In case of mains failure, the UPS can supply power from battery. The combination of isolated transformer, the high frequency double-converter structure and advanced DSP control makes the UPS completely immune to the disturbances of mains input and provide high-quality sine wave power.
  • Page 5: Operational Principle

    1.3 Operational principle...
  • Page 6 主路开关 旁路开关 维修旁路 输出开关 电池开关 MAINS SWITCH BYPASS SWITCH MANUAL BYPASS SWITCH OUTPUT SWITCH BATTERY SWITCH 警告:非专业人员请不要开启此档板 9 10 11 12 Back view Right side view 1. Fan 2. RS232 interface 3. SNMP 4. Dry contact interface 5. RS485 interface 6.
  • Page 7 Back view Right side view 后视图 右视图 1. Terminal block 2. Fan 3. RS232 interface 4. SNMP card 5. Dry contact interface 6. RS485 interface 7. Main input breaker 8. Bypass breaker 9. Repair breaker 10. Output breaker 11. Battery breaker 12.
  • Page 8: Operation Mode

    1.5 Operation mode Line mode When the mains input is normal, rectifier works to power the inverter and charge the battery. (Figure 1-8)
  • Page 9: Basic Function

    Figure 1-11 Notice: 1. The output voltage interruption time of 20kva ECO mode is less than 25ms; 2. The output voltage interruption time of 30-40kva ECO mode is less than 8ms; Make sure your load can withstand such power interrupt time. Dual inputs support The series UPS supports dual input, that means mains input and bypass input can be separated power supplies.
  • Page 10: Specification

    【Restart when mains input restore function】 The UPS can automatically restart when mains input restore in the case when UPS shuts down for battery exhausting. The combination of this feature and SNMP supervision makes the UPS work fine without artificial operation. 【...
  • Page 11 Model Efficiency Line mode > 83% (Full linear load) Battery mode > 88% (Full linear load) Overload function Overload warning only; 105%±5%≤load 2Min, then transfer to bypass and alarm; 105%±5%<load≤125%±5% Line mode/ Battery mode 30S, then transfer to bypass and alarm; 125%±5%<load≤150%±5% 0.5S, then transfer to bypass and alarm;...
  • Page 12 Model Environment Working temperature 0℃~40℃ Altitude <1000m Noise ≤70dB Storage temperature -15℃~45℃ Work humidity 20%~95% Standard EMS/EMI Conduction IEC62040-02 Anti-interference IEC 61000-4-2.4.5 Level IV, IEC61000-4-3 Level III EN55022 Radiation Class A Safety Safety GB4943-2001/IEC62040-1 Mechanical properties Connection Input Terminal blocks Output Terminal blocks Battery interface...
  • Page 13: Chapterⅱ Installation

    ChapterⅡ Installation 2.1 Environmental requirements ■ Operating Temperature: 0~40℃ ■ Storage temperature: -15℃~45℃ ■ Relative Humidity: 0%~95% ■ Cooling Mode: forced air cooling ■ The Altitude: <1000m ■ Verticality: No vibration and the slope should be less 5°. ■ Pollution Level: Grade Ⅱ UPS systems should be installed in the clean, cool and ventilated environment.
  • Page 14: Transport

    Figure 2-1 20-30KVA UPS power supply Dimensions 2.4 Transport Lifting Transport 【Preparation】Two at least 3 meters long, bearing at least 1.5 tons of the cables. 【Transportation】 The UPS power supply cabinet should transport to the installation site before removing the packages, Lifting the two suspension ropes from the bottom.
  • Page 15: Terminal Block Connect

    2.6 Terminal Block connect Terminal block of the Series UPS locates at the rear panel with a cover plate for protection. The indications of wiring are listed in Figure 2-3. PE R N PE MAINS BYPASS BATTERY INPUT INPUT OUTPUT INPUT Figure 2-3 Mode of Inlet and outlet 2.7 Ventilation...
  • Page 16: Chapterⅲ Wiring

    Sectional area of Neutral line should be 1.5~1.7 times as the one of phase line. While sectional area of PE (protective earth) line should be 0.5~1.0 times as the one of phase line and be larger than 10mm The UPS 10-20K current and cable sectional area are listed in Table 3-2. 20KVA...
  • Page 17: Cable Connection

    ◆Caution◆ Voltage of the battery breaker should meet the following requirements for reliable operation: The UPS 20-40K ≥ 450VDC. 3.1.3 Signal wire Signal wire should be shielded multi-conductor cable. 3.2 Cable connection 3.2.1 Power Cable Mains input and bypass input shares the same input in our factory to support single AC input. Figure 3-1 indicates that the customer does not have to connect bypass.
  • Page 18 ◆Caution◆ 1. All switches should be in the "OFF" state before wiring. 2. Install the recovery plate of the block terminal for good ventilation. 3. PE should be connected because of big leakage current for safety. The resistance between cabinet and Earth should be less than 1Ω.
  • Page 19 Figure 3-5 RS485 ports Pin 1: Positive bus Pin 2: Negative bus Pin 4: Shielded ground Pin3: Do not connect Dry Contact Interface Definition of dry contact interface is shown in figure.
  • Page 20 Pin Definition: Specifications Input and output UPS FAULT Output UPS ALARM Output Input REMOTE SHUTDOWN Input COMMON Output BYPASS ON Output LOW BATTERY Output UPS ON Output MAINS INPUT ABNORMAL Output REMOTE ON Input ◆Note ◆ 1. Pin4 and Pin10 are used for remote control. When Pin4 or Pin10 receives a high pulse of 3-10s, UPS will be shutdown or turned on (Signal less than 3s or longer than 10s is invalid).
  • Page 21: Chapterⅳ Power On And Debugging

    ChapterⅣ Power On and Debugging 4.1 Preparation 4.1.1 Input breaker description Mains input breaker Q1 --- Switch on/off mains input voltage Bypass breaker Q2--- Switch on/off bypass AC, to the bypass STS Repair breaker Q3--- Switch on/off connection between bypass and output Output breaker Q4--- Switch on/off UPS output Battery breaker B1--- Switch on/off battery ◆...
  • Page 22: Function Test

    4.2 Function test Check the LCD display information, LED status in lime mode/ battery mode/bypass mode. 4.2.1 LCD display and control panel Figure 4-1 shows description of key and LED Figure 4-1 Description of key and LED Switch off Q1 to simulate mains input failure, the UPS will transfer to battery mode. Check the buzzer, LED, and LCD display information.
  • Page 23: Chapterⅴ Lcd Panel Operation

    ChapterⅤ LCD panel operation 5.1 LCD panel 5.1.1 Description Description of LCD panel is shown in Figure 5-1. 1. LCD screen 2. Line LED 3. Rectifier LED 4. Battery LED 5. Bypass LED 6. Inverter LED 7. Fault LED 8. Emergency Power Off (EPO) 9.
  • Page 24: Display Information Details

    Figure5-2 LCD panel function area 5.1.2 LED display area There are six LEDs to indicate the status of UPS (Figure 5-2). 【Bypass LED】: ON means bypass is working, OFF means bypass is normal but isn't working, flashing means bypass is abnormal. 【Line LED】: ON means mains input is normal, OFF means mains input absence, flashing means mains input is abnormal.
  • Page 25 Figure 5-3 Rated information 5.2.2 Main menu After initialization and self-diagnosis, LCD displays main menu as shown in figure 5-4. Figure5-4 Main menu 5.2.3 Main menu information The main menu consists of 8 submenu item:input status、output status、operation status、fault record、rated information、system control、system setup、function setup. Users can press “UP” or “DOWN” Key to select item, “ENTER”...
  • Page 26 Figure5-5 Input status 【Output status】: LCD displays phase voltage, line voltage, load percentage, apparent power, active power and output frequency. Figure 5-6 Output status 【 Operation status 】 LCD displays battery voltage, charge or discharge current, working mode and internal temperature.
  • Page 27 Figure5-8 Fault record 【Rated information】: LCD displays UPS type, rated power, rated input/output voltage, frequency, rated battery voltage and software version. Figure 5-9 Rated information 【System control】: LCD displays turn on UPS, turn off UPS, delete fault record. Figure 5-10 system control 【System setup】: LCD displays output voltage setup, output frequency setup, battery setup, ECO and EPO setup, change password setup、recovery to default setup.
  • Page 28: System Control

    Figure 5-11 System setup 【 Function setup 】 : LCD displays time setup, ups turn on at fixed time 、 ups turn off at fixed time 、 buzzer setup、language setup. Figure 5-12 function setup 5.3 System control System control menu includes three functions: turn on UPS, turn off ups, delete fault record. Figure 5-13 System control...
  • Page 29 5.3.1 Turn on UPS Use “UP” key or “DOWN” key to choose “turn on UPS” submenu and press “ENTER” key to execute it, LCD will display “UPS is starting” (Figure 5-14); If UPS is successfully started, LCD displays “output status” page. At present, UPS is working in line mode or battery mode, output parameters are displayed in the LCD.
  • Page 30 Figure 5-16 UPS shutdown Figure 5-17 Output status 5.3.3 Delete fault record Similarly, use “UP” key and “DOWN” to choose “delete fault record” and press “ENTER” key to execute it, LCD will display “fault record has been deleted”(Figure 5-18) and all the historical records are deleted. Customer can press “ESC”...
  • Page 31: System Setup

    5.4 System setup Password is required to access “system setup”. The original password is “0000”. “UP” and “Down” key are used to change the input number and “Enter” key is used to confirm current number. “System setup” contains 7 sections: output voltage setup、output frequency setup、battery setup、ECO and EPO setup、change password setup、...
  • Page 32 Figure 5-21 Output voltage setup Figure 5-22 Save the setting 5.4.2 Output frequency setup 2 kinds of frequency are available: 【50Hz】and【60Hz】. Press “enter” key to confirm the select and remember save the setting when exit setup. Figure 5-23 Output frequency setup...
  • Page 33 5.4.3 Battery setup Battery setup consists of 2 sub functions: 1) 【 Battery number 】 : The default battery number is 32. However, chances are that customer need decrease battery. Use this function to set battery number to 30 or 31, the UPS will automatically adjust float charging voltage.
  • Page 34 Figure 5-25 ECO setting Notice: 1. The output voltage interruption time of 20kva ECO mode is less than 25ms; 2. The output voltage interruption time of 30-40kva ECO mode is less than 8ms. 5.4.5 EPO mode EPO means emergency power off. In normal situation, UPS still has output voltage even turned off if bypass voltage is normal.
  • Page 35: Function Setup

    Figure 5-27 Password change Remarks: 1. The initial password of the series ups power supply is 0000. 2. We have a common password, please contact with your agency if you forget the newly setting password. 5.4.7 Restore default setting If this command is conducted, all the parameter in “system setup” and “function control” excluding local time setting will be restored to default status.
  • Page 36 Figure5-29 Function setup 5.5.1 Time setup When changing parameters, “UP” key increases setting number, “DOWN” key decreases setting number, “ENTER” key moves the cursor right. Figure 5-30 Time setup 5.5.2 Turn on UPS at fixed time There are 3 sections in the setup of turn on UPS at fixed time. 【Status】: Enabled or disabled.
  • Page 37 Figure 5-31 Turn on UPS at fixed time 5.5.3 Turn off UPS at fixed time. There are 3 sections in the setup of turn off UPS at fixed time. 【Status】: Enabled or disabled. It’s used to enable or disable this function. Default status is “disabled”. 【Period】: It can be set from Monday to Sunday.
  • Page 38 Figure 5-33 Buzzer Beeping 5.5.5 Language setup At present, two kinds of language are available: Mandarin and English. Figure 5-34 Language setup...
  • Page 39: Ups Alarm And Display

    5.6 UPS alarm and display When UPS is abnormal or faulty, it will show the related sound and light alarm, and the fault record will be automatically saved for uses to review. Fault Fault reason Sound alarm Solution directions Red light Output short-circuited Beep Please check the load...
  • Page 40: Chapter Vi Operate And Maintenance Guide

    Chapter VI Operate and maintenance guide This chapter describes UPS normal operation and routine maintenance; Before UPS any internal operation, switch off main breaker Q1, bypass breaker Q2, battery breaker B1 and wait for 5 minutes to make the capacitors discharge to safe voltage.
  • Page 41: Maintenance Guide

    6.1.6 Failure review The series UPS has self-diagnosis capability; you can check the fault type in the front LCD or by software. Low battery voltage shutdown UPS will shut down for low battery voltage in battery mode. It will automatically be turned on if the AC input recovers.
  • Page 42: Chapter Vii Fault Diagnosis

    Chapter VII Fault diagnosis 7.1 Fault diagnosis procedure 【Status record】Record the LCD display content, buzzer sound, LED indications and status of input breaker when UPS fault occurs. 【Fault type identification】Refer to the fault table to confirm fault type. If the fault is not mentioned in the table, contact your vendor or technical support engineer for further information.
  • Page 43: Chapterⅷ Battery Maintenance

    ChapterⅧ Battery maintenance 8.1 Battery 8.1.1 Cautions 1. All battery installation and maintenance should be conducted by qualified personnel. 2. Verify the battery appearance before installation and use, replace the battery if package damage, corrosion or acid leakage occurs to avoid resulting in reduced battery capacity, leakage, fire and other accident. 3.
  • Page 44: Chapterⅸ Service

    ChapterⅨ Service 9.1 Exception Handling If UPS is abnormal but shows no fault or alarm, refer to the table below for troubleshooting. Table 9-1 trouble shooting Description of the Possible reasons Handing method phenomenon A: Mains input not well connected Mains input switch and or voltage not correct.
  • Page 45: Appendixⅰ Start And Shutdown Ups Operation Process

    AppendixⅠ Start and shutdown UPS operation process AppendixⅠ1.1 Procedures of UPS on 1. Switch on the power input breaker 2. Switch on the battery breaker B1 3. Switch on the mains input breaker Q1 4. Switch on the bypass breaker Q2 5.

This manual is also suitable for:

30k40k

Table of Contents