Wiring

Important points to remember about wiring:
• Always use copper wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control wires should be separated from power wires by at least 0.3
meters (1 foot).
Safe-Off with Second Encoder Terminal Block Specifications
(1)
Wire Size Range
Maximum
2
1.5 mm
(16 AWG)
(1)
Maximum / minimum that the terminal block will accept - these are not
recommendations.
Wire Types
Wire Type(s)
Unshielded Per US NEC or applicable
national or local code
Shielded
Multi-conductor shielded cable
such as Belden 8770(or equiv.)
Safe-Off Terminals Description
A S S E M B LY
I D L A B E L
B A R
C O D E
L A B E L
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9 10
11
12
13
Minimum
2
0.14 mm
(26 AWG)
No. Signal
1
+24V DC
2
24V Common
3
Monitor - N.C.
4
Common - N.C.
Installation and Wiring
Torque
Maximum
0.25 N-m
(2.2 lb.-in.)
Description
2
0.750 mm
(18AWG),
3 conductor, shielded.
Description
Connections for user supplied power
to energize coil.
33.3 mA typical, 55 mA maximum.
Normally closed contacts for
monitoring relay status.
Maximum Resistive Load:
250V AC / 30V DC / 50 VA / 60 Watts
Maximum Inductive Load:
250V AC / 30V DC / 25 VA / 30 Watts
11
Recommended
0.22 N-m
(1.9 lb.-in.)
Minimum
Insulation Rating
300V,
60 degrees C
(140 degrees F)