Connect Control Power
Wiring
Top Entry Design
Introduction
Externally supplied control power is required to operate the drive. The standard
voltage that is supported is 220V AC/50 Hz. The other typical phase voltages of
230V AC, 110V AC, and 120V AC are also supported (50/60 Hz), but need to
be specified at the time of order. A minimum of 3 kVA is required to supply the
control circuit.
Wiring Routing and Connection
The opening for the control power wiring must be specified during the quotation
stage. See the customer-specific Dimension Drawing for the location of the
opening. The typical top/bottom entry design is shown below
Figure 33 - Control Power Wiring Opening, A-Frame
Cable entrance in top
of LV Control Cabinet
Wire duct for
bundling cable
Bracket for
bundling cable
Cable entrance in bottom
of LV Control Cabinet
Figure 34 - Control Power Wiring Opening, H-Frame
Cable entrance in top
of LV Control Cabinet
Rockwell Automation Publication 6000-IN006G-EN-P - September 2019
Cable entrance in bottom
rear of LV Control Cabinet