Wiring Routing And Connection - Allen-Bradley 6000G Installation Manual

Medium voltage variable frequency drive
Table of Contents

Advertisement

Connect Control Power
Wiring
Top Entry Design
Introduction
Externally supplied control power is required to operate the drive. The standard
voltage that is supported is 220V AC/50 Hz. The other typical phase voltages of
230V AC, 110V AC, and 120V AC are also supported (50/60 Hz), but need to
be specified at the time of order. A minimum of 3 kVA is required to supply the
control circuit.

Wiring Routing and Connection

The opening for the control power wiring must be specified during the quotation
stage. See the customer-specific Dimension Drawing for the location of the
opening. The typical top/bottom entry design is shown below
Figure 33 - Control Power Wiring Opening, A-Frame
Cable entrance in top
of LV Control Cabinet
Wire duct for
bundling cable
Bracket for
bundling cable
Cable entrance in bottom
of LV Control Cabinet
Figure 34 - Control Power Wiring Opening, H-Frame
Cable entrance in top
of LV Control Cabinet
Rockwell Automation Publication 6000-IN006G-EN-P - September 2019
Cable entrance in bottom
rear of LV Control Cabinet
Bottom Entry Design
Drive Electrical Installation
Chapter 2
(Figure
34).