or nC or nO
E
EA OFF
or OFF or Int
F
dF On
G
dA
00
or OFF
H
LO ON
or FAN
J
PULSE
Red fixed light
In the Fan start mode
Start signal
In the Pre-coate mode
ST
PA
IN
Start signal
1
0
1
0
00 - 60 s
1
0
1
0
1
0
Stop signal
PA
IN
PA
Stop signal
Fire alarm
0
Push the P-button.
1
Activated input: JP1: 7
Set OFF, nC or nO with the 0/1-button
OFF
nC
Dust feeder
Push the P-button.
0
Activated output: JP6: 3
Direct controlled by contactor or other 24 V relay.
1
On: The dust feeder is in operation
OFF: The dust feeder is not in operation
Int: Intermittent operation of the dust feeder
Set On, OFF or Int with the 0/1-button.
On
OFF
Down time damper delay
0
Push the P-button.
1
Activated output: JP6: 2
24 V AC supply for opening a damper motor with
spring return or magnetic valve for compressed air.
Is used to reduce the starting current at fan start.
Delay time for opening the down time damper:
10 - 60 s after fan start. Set the required delay time
with the 0/1-button.
Local START/STOP
0
Push the P-button.
1
Activated input: JP1: 1
Inactivates the start/stop button on the control box.
Only remote start is possible in OFF-position.
Set On or OFF with the 0/1-button.
On
OFF
Pre-Coate Control
0
In some applications with FilterMax it is necessary to inject
1
dust. The purpose can be to reduce the fire risk or improve
cleaning of the filter cartridges. The input JP6:1 can be
used in 2 ways. When the function of the motor protection
has been chosen, the fan LED will show fixed red light.
Then you are able to choose the use of JP6:1 PULSE or
FAN with the 0/1-button. PULSE is the pre-coate mode.
PULSE
FAN
If PULSE is set there will be a choise of parameters to set:
ST - Start. The initial injection time: 0, 1, 2, 3, 4, 5, 7, 10,
15, 20, 30, 40, 60 or 90 s.
IN - Injection. The injection time: 0, 1, 2, 3, 4, 5, 7, 10, 15,
20, 30, 40 or 60 s.
PA - Pause. The pause time between the injections: 0 or
20 s. 1, 2, 5, 10, 20 or 60 min.
If FAN is set JP6:1 will run in parallel with JP6:8,9 serving
as a 24 V fan start signal.
nO
Int
11
Need help?
Do you have a question about the FilterMax F Series and is the answer not in the manual?