Volkswagen Amarok 2011 Workshop Manual page 150

Hide thumbs Also See for Amarok 2011:
Table of Contents

Advertisement

Amarok 2011 ➤ , Beetle 2012 ➤ , Bora 1999 ➤ , CC 2010 ➤ , CC 2012 ➤ , ...
Air conditioning system with refrigerant R134a - Edition 10.2014
Low-pressure side:
Falling from starting pressure (when pressure gauge is connec‐
ted) to diagram value.
A - Low pressure (measured at the service connection) in bar ab‐
solute pressure.
B - Control current for the air conditioner compressor regulating
valve - N280- .
C - Permitted tolerance range.
Note
Under unfavourable conditions (very high ambient tempera‐
tures, high atmospheric humidity), the pressure on the high-
pressure side can increase to a maximum of 29 bar.
The control current -B- is indicated in the measured values
block.
The high pressure is indicated in the measured values block
⇒ Rep. gr. 87 .
The low pressure is adjusted to within tolerances within the
output range for the air conditioner compressor depending on
the control current for the air conditioner compressor regulat‐
ing valve - N280- .
Under unfavourable conditions (very high ambient tempera‐
tures, high atmospheric humidity), the output may be insuffi‐
cient to achieve the specification in every case.
The set working current for the regulating valve must be great‐
er than 0.3 A to ensure that the regulating valve is reliably
activated.
At the setting for "maximum cooling power", the control current
should be approx. 0.8 A (indicated in the measured values
block) ⇒ Rep. gr. 87 .
Absolute pressure means that 0 bar corresponds to an abso‐
lute vacuum. The normal ambient pressure corresponds to 1
bar absolute pressure. On most pressure gauges, a reading
of 0 bar corresponds to an absolute pressure of one bar (which
is confirmed by the existence of - 1 bar marking beneath the
0 scale marking).
144
Rep. gr.00 - Technical data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents