Modbus Registers - Banner EZ-LIGHT K70 Series Manual

Wireless indicator light
Table of Contents

Advertisement

®
Sure Cross
User Configuration Software
The User Configuration Software offers an easy way to link I/O points in your wireless network, view I/O register values, and set
system communication parameters when a host system is not part of the wireless network. The software runs on any computer
with the Windows Vista, Windows 7, Windows 8, or Windows 10 operating system.
Creating Flash Patterns
Use the User Configuration Tool (UCT) to set the Duty Cycle, For Outputs of Node 1, output 9, to 0x0F0F as shown below, to
achieve this flash pattern.
Flash a K70 light by entering a time-based bit mask into the Duty Cycle parameter for that output register. Bit 0 represents the first
62.5 ms time window, bit 1 represents the second 62.5 ms window, etc.
For example, turn ON the output from 0 to 250 ms, OFF from 250 to 500 ms, ON from 500 to 750 ms, then OFF again from 750 ms
to 1 second by writing 0x0F0F to the appropriate output.
Bit
15
14
13
Bin
0
0
0
Hex
0
Light
Turned off from 750 ms to 1 s
This example shows 0F0F being written to the Duty Cycle, For Outputs parameter for Node 1, output 9.

Modbus Registers

I/O
Modbus Holding Register
Gateway
Any Node
1
1
1 + (Node# × 16)
2
2
2 + (Node# × 16)
3
3
3 + (Node# × 16)
4
4
4 + (Node# × 16)
5
5
5 + (Node# × 16)
6
6
6 + (Node# × 16)
6
Use a USB to RS-485 adapter cable to connect a standalone DX80 Gateway to the
computer. For DXM Controllers with an internal DX80 radio, connect a computer to the
DXM Controller using a USB or Ethernet connection. Download the most recent revisions
of the configuration software from Banner Engineering's website:
www.bannerengineering.com/wireless.
The USB to RS-485 adapter cable is not required for the DXM Controller. For standalone
DX80 Gateway devices use:
USB to RS-485 adapter cable model BWA-UCT-900 for 1 Watt radios
USB to RS-485 adapter cable model BWA-HW-006 for all other radios
12
11
10
9
0
1
1
1
F
Turned on from 500 to 750 ms
I/O Type
Discrete IN 1 / Bit-packed inputs
Discrete IN 2
Discrete IN 3
Discrete IN 4
Discrete IN 5 / 32-bit event counter high word
Discrete IN 6 / 32-bit event counter low word
www.bannerengineering.com - Tel: + 1 888 373 6767
8
7
6
5
1
0
0
0
0
Turned off from 250 to 500 ms
I/O Range
Min.
Max.
0
1
0
1
0
1
0
1
0
1
0
1
®
EZ-LIGHT
K70 Wireless Indicator Light
4
3
2
1
0
1
1
1
F
Turned on from 0 to 250 ms
Holding Register
Color #
Representation (Dec.)
Min.
Max.
0
1
0
1
0
1
0
1
0
1
0
1
P/N 192534 Rev. D
0
1
C1
C2
C3
C4
C5
-