Figure 28: Genius Discrete Block Failed Switch Fault Display (Example)

Table Entry
Explanation
Loc
Location of Fault
Circ No.
Genius Device Circuit #
Variable Name
Alternate to Ref Address
Ref. Address
PLC Reference Address
Fault Category
Coded Fault Category
Fault Type
Coded Fault Type
Date/Time
Date/Time

Figure 29: Genius Analog Block Over Range Fault Display (Example)

Clearing the RX3i Fault Tables

Clearing the RX3i CPU's I/O fault tables has no effect on the GCG001 or on the Genius Devices downstream
from it. This action merely clears the I/O Fault Table temporarily. Use the Genius HHM or COMREQs in the PLC
program to exercise I/O points that had previously exhibited faults, and where the underlying field fault
condition has already been corrected.
GFK-2892F
Value
Interpretation
0.6.D1.r0.s15.ss1
Rack 0 Slot 6 = location of PNC
D1 = Device Number of GCG
s15 = SBA of faulted Genius device
ss1 (Not used for Genius blocks. VersaMax,
90-70 Scanner rack, and Field Control
devices specify the location of module in
fault.)
5
Fifth point on the Genius device is faulted
Will display if variable name has been
assigned
%QI 00145
Point 145 in %QI table is referenced
Channel Diagnosis
Appears when fault first detected at PLC.
Appears/Disappears"
Disappears when fault has been resolved.
Manufacturer specific
See table of Fault Types (page 46).
(273)
Failed Switch in this case
Date/Time fault is registered by PLC.
March 2019
Chapter 5. Diagnostics