COMMREQ #6: Clear All Circuit Faults Command

The Clear All Circuit Faults command is used to clear all faults on a targeted Genius I/O device.
Command Block for the Clear All Circuit Faults Command
Address
Command Length
Address +1
No Wait
Address +2
Status Block memory type
Address +3
Status Block offset
Address +4
Idle timeout value
Address +5
Max. communications time
Address +6
Command number
Address +7
PROFINET Device number
Address +8
Genius Device Number
7
This enhancement (use of 255 as Genius Device Number) requires that the supervising PNC001 firmware be version 2.11
or later; otherwise the COMMREQ command will fail. If CPE330 is used, firmware version 8.80 is required. If CPE400 is
used, all firmware versions support this functionality.
GFK-2892F
Chapter 6. COMMREQ/Data_Init_Comm Programming
3
0
70 (%I), 72 (%Q), 8 (%R), 10 (%AI), 12 (%AQ) or 196 (%W)
Beginning address for the COMMREQ Status Block.
0
0
6
1-255: The device number of the targeted GCG Genius Gateway.
1-29 or 255: the SBA of the targeted Genius Device.
Enter 255 to send this command to all blocks on the bus.
March 2019