Chapter 6. COMMREQ/Data_Init_Comm Programming
I/O Data Format Returned by Current Source Output (CSO) Blocks
Byte #
Description
0
Block Model Number
1
Block Software Revision Number
2
µA commanded value for output channel 1 (LSB)
3
µA commanded value for output channel 1 (MSB)
4-5
µA commanded value for output channel 2
6-7
µA commanded value for output channel 3
8-9
µA commanded value for output channel 4
10-11
µA commanded value for output channel 5
12-13
µA commanded value for output channel 6
14
Engineering Units value for output channel 1 (LSB)
15
Engineering Units value for output channel 1 (MSB)
16-17
Engineering Units value for output channel 2
18-19
Engineering Units value for output channel 3
20-21
Engineering Units value for output channel 4
22-23
Engineering Units value for output channel 5
24-25
Engineering Units value for output channel 6
I/O Data Format Returned by Current Source Input (CSI) Blocks
Byte #
Description
0
Block Model Number
1
Block Software Revision Number
2
µA value for input channel 1 (LSB)
3
µA value for input channel 1 (MSB)
4-5
µA value for input channel 2
6-7
µA value for input channel 3
8-9
µA value for input channel 4
10-11
µA value for input channel 5
12-13
µA value for input channel 6
14
Engineering Units value for input channel 1 (LSB)
15
Engineering Units value for input channel 1 (MSB)
16-17
Engineering Units value for input channel 2
18-19
Engineering Units value for input channel 3
20-21
Engineering Units value for input channel 4
22-23
Engineering Units value for input channel 5
24-25
Engineering Units value for input channel 6
78