Figure 14: Hardware Configuration Expanded Tree; Figure 15 - Gcg Data Reference Addresses; Figure 16: Genius Gateway Parameters - GE GFK-2892F User Manual

Pacsystems rx3i genius communications gateway
Table of Contents

Advertisement

Chapter 3. Configuration
7.
geniusgateway...
now appears
(Figure 14) as an IO
device in the
Hardware
Configuration tree
under the PNC001.
8.
Within the
geniusgateway
branch, two daughter devices
are displayed by default: the
GCG (shown in Figure 16 at slot 0 with its connected PNC) and the Gateway module itself at slot
31. You may drag the gateway to slot 30, if desired.
Note that slot 0, normally used by the Genius HHM, is not really consumed by the GCG001. The
slot 0 indication for the GCG001 in the PME display should be ignored: no I/O module may be
dragged into the slot.
Note:
geniusgateway... is the default PROFINET Device Name that PME gives to a GCG001 in
the Hardware Configuration under a PNC001. This Device Name must match that given
to the module itself using the PROFINET/DCP (Discovery and Configuration Protocol) tool
(Figure 12). If there are multiple GCG001s on a PROFINET bus, each of the modules'
Device Names must be unique. You can change it by selecting the device in the
Navigator, then typing in a new name in the Inspector.
Example: GCG_inside and GCG_outside are acceptable Device Names.
9.
Enter the reference addresses for Genius Status Data, Fault Status Data, and Gateway Status
10. If desired, change the GCG001 configuration parameters for Genius Bus Baud Rate and Output at
Startup (Figure 16). Select the GENIUS Gateway Module in slot 31 (or slot 30) and double-click it.
You can now use the pull-down menus to select the appropriate Baud Rate and Output at Startup
value.
When Output at Startup is set to Disabled, no output data is sent to the Genius devices when the
PLC transitions from STOP to RUN. In this case, the Enable/Disable Outputs COMMREQ must be
used to enable outputs on the Genius bus.
28

Figure 14: Hardware Configuration Expanded Tree

Data.

Figure 15 - GCG Data Reference Addresses

Figure 16: Genius Gateway Parameters

PACSystems RX3i Genius Communications Gateway