Connecting The Mains Supply To Systems With Direct-On-Line Starting; Connecting The Mains Supply To Systems With Star-Delta Starting; Installing The Lifting Station; Location - Grundfos Multilift MD1 Installation And Operating Instructions Manual

Hide thumbs Also See for Multilift MD1:
Table of Contents

Advertisement

3.1.3.1 Connecting the mains supply to systems with direct-on-line starting

Make sure that the supply voltage and frequency correspond to the values stated on the
nameplate on the lifting station.
If required according to local regulations, install an external all-pole main switch.
If required according to local regulations, install a backup fuse. See the controller name-
plate.
Systems with direct-on-line starting have a 1.5 m power supply cable connected in the control
cabinet. The cable is equipped with a CEE plug.
1. Install a CEE power socket less than 1.5 m from the control cabinet.
2. Connect the CEE plug to the CEE power socket.
Related information
• 6.2.1 Nameplate

3.1.3.2 Connecting the mains supply to systems with star-delta starting

Make sure that the supply voltage and frequency correspond to the values stated on the
nameplate on the lifting station.
If required according to local regulations, install an external all-pole main switch.
If required according to local regulations, install a backup fuse. See the controller name-
plate.
Systems with star-delta starting have an all-pole main switch on the cabinet front.
1. Set the main switch to off.
2. Connect a power supply cable to the control cabinet through the cable entries and gaskets.
See the wiring diagram.
3. Set the motor-protective circuit breakers in the control cabinet.
Related information
• 6.2.1 Nameplate

3.2 Installing the lifting station

3.2.1 Location

Install the product in a location that meets the following requirements:
Make sure that the location is properly lit.
Make sure that the location is properly vented.
Make sure that there is at least 60 cm free space around the product.
We recommend that you install a drainage pump in a pump sump below floor level if you
install the lifting station in a basement with the risk of penetrating groundwater. In some
countries, a drainage pump or only a pump sump is required. We also recommend that you
install a separate float switch next to the lifting station and connect it to terminals 13 and 14
of LC 221. If the float switch is activated, the controller gives an acoustic alarm, the display
shows the external alarm EXTERN, a red LED flashes, and the common fault relay is activa-
ted.
The lifting station may be flooded maximum 2 metres for seven days.
Multilift MD1, MDV | | 9