Baxi NUVOLA 28 Fi Installers And Users Instructions page 17

High efficiency, fast-heating gas boilers with balanced flue for wall-mounting
Table of Contents

Advertisement

VERTICAL BALANCED FLUE WITH AIR FROM
EXISTING DISUSED CHIMNEY
Where indicated by the conditions, use the aforementioned VERTICAL
balanced flue – which means that the air is taken in via an existing disused
chimney and the flue gas is directed out at the same place (through the
cover (for the balanced vertical flue) which allows the air to go down
through an existing chimney).
The connecting set for flue/air via a chimney consists of:
1 top section for the chimney
1 roof duct with cover
1 split connecting set Ø 80.
In addition, the following must be used:
Straight pipe Ø 80 for air or flue gas (use a rust-resistant pipe for flue
gas, an aluminium pipe for air)
Maximum total length of air + flue = (10 + 10) m minus 1 m for each
90° bend (0.5 m for each 45° bend)
15°, 30°, 45° or 90° bend (use rust-resistant for flue gas, aluminium for
air)
Wall bushes
If necessary, pipe clamps for flue pipe and air pipe
Silicone
If necessary, condensation trap
Installation of vertical balanced flue, where the existing disused
chimney is used to carry the flue gas pipe and to convey air
The chimney must be disused and must be
cleaned very carefully in order to prevent
dirt being sucked into the gas boiler.
Minimum diameter of the chimney Ø 130
Maximum total length of air + flue = (10 +
10) m minus 1 m for each 90° bend (0.5 m
for each 45° bend)
1. Use silicone or similar for a water-tight
joint.
2. Screw the top section securely on top of the
chimney.
3. Fit the flue pipes to the "roof duct with
cover", and lower all of the pipes into the
chimney. (If necessary, secure the joints
with self-tapping, rust-resistant screws or
pop rivets (not provided).)
4. Attach the split connecting set to the boiler
as shown elsewhere in these instructions.
5. The pipe is taken from the flue pipe in the
chimney to the boiler
6. Air intake is taken to the chimney either
above or below the flue outlet.
7. The air intake must be secured so that it
cannot be moved, thereby restricting the air
intake in the chimney and boiler.
Distance from flammable materials must be
as laid down in the Gas Regulations
regarding a flue duct (section 5.5), that is to say:
On all sides there must be a clearance of at least 50 mm from the outer
edge of the flue pipe to flammable materials.
The flue pipe MUST be insulated with a minimum of 25 mm mineral
wool* from and including the first wall duct up to and including the
end.
The mineral wool insulation must be taken through the flammable
material and, if necessary, end at least 100 mm from it.
L 3 System
LODRET BALANCERET AFTRÆK MED LUFT FRA
EKSISTERENDE AFMELDT SKORSTEN
Hvor forholdene taler herfor anvendes ovennævnte LODRET balanceret
aftræk - hvorved forstås at luften tages ind via afmeldt eksisterende afmeldt
skorsten og røggas ledes ud samme sted (Gennem hætte (for balanceret
lodret aftræk) der lader luften gå ned gennem en eksisterende, afmeldt
skorsten).
Tilslutningssæt aftræk/luft via skorsten består af:
1 stk. Topstykke til skorsten.
1 stk. Taggennemføring m. hætte.
1 stk. Split tilslutningssæt Ø80.
Desuden skal bruges:
Lige rør Ø80 til luft eller røggas (Til røggas skal anvendes rustfri, til
luft anvendes aluminiumsrør)
Max totallængde af luft+aftræk = (10+10) m minus 1 m for hver 90 °
bøjning (0,5 m pr. 45 ° bøjning)
Bøjning 15 ° , 30 ° , 45 ° eller 90 ° (Til røggas skal anvendes rustfri, til luft
anvendes aluminiumsrør)
Murbøsninger
Evt. rørbærer for røgrør og luftrør
Silikone
Evt. kondensfang
Montage af lodret balanceret aftræk, hvor den eksisterende afmeldte
skorsten anvendes til føring af røggasrør og til lufttransport.
Roof duct with cover
Taggennemføring m/hætte
Cap for chimney
Top til skorsten
Pipe Ø80 (rust-resistant)
Rør Ø80 (rustfri)
90° bend Ø80 (rust-resistant)
Bøjning 90 ° Ø80 (rustfri)
Wall bushes
Murbøsninger
Vertical connecting set
Split tilslutningssæt
Afstand til brændbart matr. skal være som Gasreglementet foreskriver
vedr. aftrækskanal (afsnit 5.5) Det vil bl.a. sige:
Der skal overalt være en afstand på mindst 50 mm fra yderkant røgrør
til brændbart materiale.
Aftræksrøret SKAL isoleres med min. 25 mm mineraluld* fra og med
første murgennemføring til og med afslutning.
Mineraluldsisoleringen skal føres med igennem brændbart matr. og
17
921.968.2.00.02.010702
System L3
Skorstenen skal være afmeldt og
skal være renset meget omhyggeligt
for at undgå, at der suges snavs ind i
gaskedlen.
Minimum diameter af skorsten Ø
130
Max totallængde af luft+aftræk =
(10 + 10) m minus 1 m for hver 90 °
bøjning (0,5 m pr. 45 ° bøjning)
1. Benyt silikone el. lign. for vandtæt
samling.
2. Topstykket skrues forsvarligt på top
af skorsten.
3. Røgaftræksrørene monteres på
"taggennemføring m. hætte", og alle
rørene sænkes ned i skorstenen.
(Samlingerne sikres evt. med
selvskærende rustfri skruer eller
popnitter (medfølger ikke)
4. Split tilslutningssættet monteres på
kedlen som anført andetsteds i denne
instruktion.
5. Rør føres fra røgaftræksrør i
skorsten til kedel.
6. Luftindtag føres til skorsten, enten
over eller under røgafgang.
7. Luftindtaget skal sikres, så det ikke
kan flyttes og derved begrænse
luftindtag i skorsten og kedel.