As there is a certain loss of pressure in the double pipe A, the table indicates
the maximum height (H) in relation to the length of (A).
A (m)
0 - 1
1 - 2
H max. (m)
15
12
FITTING OF A SPLIT CONNECTING SET TO Ø80 MM PIPE
✱ If the total flue-air ducts length
exceeds 12 metres, remove the
restrictor and washer provided
with the boiler.
✱ Hvis den samlede røggas-
luftkanallængde overstiger 12
meter, skal man fjerne den ene
pakning og flowbegrænseren
leveret med kedlen.
In the following examples, the split connecting set must be fitted on the
boiler as shown on the next page.
2 - 3
9
Condensation trap
Kondensfang
921.968.2.00.02.010702
Da der er et vist tryktab i dobbeltrøret A er der i tabellen anført maksimal
højde (H) i forhold til længden af (A)
MONTAGE AF SPLITTILSLUTNINGSSÆT TIL Ø80 MM RØR
Silicone washer
På de efterfølgende eksempler skal split tilslutningssættet monteres på
kedlen som vist herover.
16
A (m)
0 - 1
1 - 2
H max. (m)
15
12
00060200300
2 - 3
9