Malfunctions - Samson 3275 Mounting And Operating Instructions

Pneumatic piston actuator
Table of Contents

Advertisement

Malfunctions

8 Malfunctions
Depending on the operating conditions, check the actuator at certain intervals to prevent
possible failure before it can occur. Operators are responsible for drawing up an inspection
plan.
Troubleshooting
Malfunction
Piston rod does not move on
demand.
Piston rod does not stroke
through its complete travel
range.
28
Possible reasons
Actuator is blocked.
Insufficient signal pressure
Signal pressure not connected
properly.
Insufficient signal pressure
Valve accessories incorrectly set.
Recommended action
Check attachment.
Unblock the actuator.
Check the signal pressure.
Check the signal pressure line for
leakage.
Check the signal pressure
routing. See section 3.
Check the signal pressure.
Check the signal pressure line for
leakage.
Check the actuator without valve
accessories.
Check the settings of the valve
accessories.
EB 8314 EN