1 INTRODUCTION
1 INTRODUCTION 1.1 OVERVIEW
a) PROTECTION
3 separate phase time overcurrent (51) elements with 5 curve shapes:
Definite time, moderately inverse, normal inverse, very inverse, extremely inverse.
Phase instantaneous (50) element
Ground time overcurrent (51G) with 5 curve shapes:
Definite time, moderately inverse, normal inverse, very inverse, extremely inverse.
Ground instantaneous (50G) element
10 curves for each shape
4 time multipliers for each curve
3 different curve types: ANSI, IAC, IEC/BS142
b) INDICATORS
Trip:
Phase A, B, C instantaneous
Phase A, B, C time overcurrent
Ground fault instantaneous
Ground fault time overcurrent
Status: Relay in service
Service required
Phase pickup
Ground pickup
Current bargraph: 10 to 100%
c) OTHER
Conventional 1 A or 5 A CT input
Drawout case
AC or DC control power
Seal provision for tamper proof settings
Output contacts:
Trip
Aux Trip
Service Required
(737 only) pickup, trip, cause of trip outputs;
50A, 50B, 50C, 50N
51A, 51B, 51C, 51N
RS485 communications: settings, currents, status
86 lockout
Programmable block instantaneous on autoreclose.
Ground Fault trip programmable to Aux. Trip relay, separate from Main trip.
GE Power Management
735/737 Feeder Protection Relay
1.1 OVERVIEW

1.1.1 FEATURES

1
1-
1