Error Responses - GE 735 Instruction Manual

Feeder protection relay
Table of Contents

Advertisement

4 MODBUS COMMUNICATIONS
MASTER TRANSMISSION:
SLAVE ADDRESS
FUNCTION CODE
DATA STARTING ADDRESS
NUMBER OF SETPOINTS
DATA BYTE COUNT
DATA #1
DATA #2
DATA #3
DATA #4
DATA #5
DATA #6
DATA #7
DATA #8
DATA #9
DATA #10
CRC
SLAVE RESPONSE:
SLAVE ADDRESS
FUNCTION CODE
DATA STARTING ADDRESS
NUMBER OF SETPOINTS
CRC
Note: for 16 bit transfers hi byte is transmitted first. For example, 0050h is transmitted 00h then 50h
When a 735/737 detects an error other than a CRC error, a response will be sent to the master. The most significant bit of
the FUNCTION CODE byte will be set to 1 (that is, the function code sent from the slave will be equal to the function code
sent from the master plus 128). The byte which follows it will be an exception code indicating the type of error that occurred.
Transmissions received from the master with CRC errors will be ignored by the 735/737.
The slave response to an error (other than CRC error) will be:
SLAVE ADDRESS: 1 byte
FUNCTION CODE: 1 byte (with MSbit set to 1)
EXCEPTION CODE: 1 byte
CRC: 2 bytes
The 735/737 implements the following exception response codes.
01: ILLEGAL FUNCTION: The function code transmitted is not one of the functions supported by the 735/737.
02: ILLEGAL DATA ADDRESS: The address referenced in the data field transmitted by the master is not an allowable
address for the 735/737.
03: ILLEGAL DATA VALUE: The value referenced in the data field transmitted by the master is not within range for the
selected data address.
06: BUSY, REJECTED MESSAGE: The transmission was received error-free but the request could not be performed.
08: MEMORY PARITY ERROR: A hardware error has occurred in the 735/737. For example, a RAM failure has
occurred and the data requested cannot be sent.
GE Power Management
BYTES
EXAMPLE / DESCRIPTION
1
11
message for slave 11
1
10
store setpoint block
2
00 60
first setpoint address 0060h
2
00 0A
10 setpoints
1
14
20 bytes of setpoint data
2
00 06
phase pickup = position 6
2
00 05
phase shape = position 5
2
00 07
phase time multiplier = 7
2
00 01
phase instantaneous = off
2
00 0A
ground pickup = 10 (100% of CT)
2
00 08
ground curve shape = 8 (very inverse)
2
00 03
ground time multiplier = 3
2
00 05
ground instantaneous = 5 (0.8 x CT)
2
00 7B
phase current = 7B (120%)
2
00 32
ground current = 32 (50%)
2
?? ??
CRC calculated by the master
BYTES
EXAMPLE / DESCRIPTION
1
11
response message from slave 11
1
10
store setpoint block
2
00 50
block start address
2
00 0A
10 setpoints (2 bytes each)
2
?? ??
CRC calculated by the slave
735/737 Feeder Protection Relay
4.2 SUPPORTED MODBUS FUNCTIONS

4.2.8 ERROR RESPONSES

4
4-9