GE 735 Instruction Manual page 59

Feeder protection relay
Table of Contents

Advertisement

4 MODBUS COMMUNICATIONS
Table 4–2: 735/737 MEMORY MAP DATA FORMATS (Sheet 2 of 5)
FORMAT
TYPE
F103
737 OUTPUT RELAYS
continued
F104
CURVE SHAPE SETPOINT
F105
LEDs
(READ ONLY)
F106
BARGRAPH
(ACTUAL VALUE)
F107
CURVE SHAPE SWITCH
GE Power Management
DESCRIPTION
XXXX XXX1 XXXX XXXX = Phase A time OC pickup/trip (51P-A)
XXXX XX1X XXXX XXXX = Phase B time OC pickup/trip (51P-B)
XXXX X1XX XXXX XXXX = Phase C time OC pickup/trip (51P-C)
XXXX 1XXX XXXX XXXX = Ground time OC pickup/trip (51G)
XXX1 XXXX XXXX XXXX = Phase A nest pickup/trip (50P-A)
XX1X XXXX XXXX XXXX = Phase B nest pickup/trip (50P-B)
X1XX XXXX XXXX XXXX = Phase C nest pickup/trip (50P-C)
1XXX XXXX XXXX XXXX = Ground nest pickup/trip (50G)
Definite time = 1
Moderately Inverse = 2
Normal Inverse = 3
Very Inverse = 4
Extremely Inverse = 5
XXXX XXXX XXXX XXX1 = Phase A overcurrent LED on = 1
XXXX XXXX XXXX XX1X = Phase B overcurrent LED on = 1
XXXX XXXX XXXX X1XX = Phase C overcurrent LED on = 1
XXXX XXXX XXXX 1XXX = Ground overcurrent LED on = 1
XXXX XXXX XXX1 XXXX = Phase A instantaneous LED on = 1
XXXX XXXX XX1X XXXX = Phase B instantaneous LED on = 1
XXXX XXXX X1XX XXXX = Phase C instantaneous LED on = 1
XXXX XXXX 1XXX XXXX = Ground instantaneous LED on = 1
XXXX XXX1 XXXX XXXX = Phase pickup LED on = 1
XXXX XX1X XXXX XXXX = Ground pickup LED on = 1
XXXX X1XX XXXX XXXX = Relay in service LED on = 1
XXXX 1XXX XXXX XXXX = Service required LED on = 1
XXXX XXXX XXXX XXX1 = 100% indicator on = 1
XXXX XXXX XXXX XX1X = 90% indicator on = 1
XXXX XXXX XXXX X1XX = 80% indicator on = 1
XXXX XXXX XXXX 1XXX = 70% indicator on = 1
XXXX XXXX XXX1 XXXX = 60% indicator on = 1
XXXX XXXX XX1X XXXX = 50% indicator on = 1
XXXX XXXX X1XX XXXX = 40% indicator on = 1
XXXX XXXX 1XXX XXXX = 30% indicator on = 1
XXXX XXX1 XXXX XXXX = 20% indicator on = 1
XXXX XX1X XXXX XXXX = 10% indicator on = 1
Definite time (low) = 1
Definite time (high) = 2
Moderately Inverse (low) = 3
Moderately Inverse (high) = 4
Normal Inverse (low) = 5
Normal Inverse (high) = 6
Very Inverse (low) = 7
735/737 Feeder Protection Relay
4.3 MEMORY MAP